7. PARAMETER
TABLE
Key:
Parameter type:
Variable type:
Noted:
C = Confi guration,
A = analogue,
•
MSYFCH = parameter visible on models IREVM%, IREVS%, IREVY%, IREVF%, IREVC% and PBEVH%;
F = frequent
I = integer,
•
The grey rows in the table denote masked parameters
D = digital
User
Par.
Description
Models
Def
Min Max UOM Type CAREL SVP ModBus®
R/W
Pro
C
/2
Probe measurement stability
MSYFCH
4
1
15
-
I
15
115
R/W
C
/3
Probe display stability
Value
Display delay (s)
Value
Display delay (s)
0
disabled
8
50
1
5
9
60
2
10
10
75
3
15
11
90
4
20
12
105
5
25
13
120
6
30
14
150
7
40
15
180
MSYFCH
0
0
15
-
I
16
116
R/W
C
/4
Virtual probe composition
0 = Control probe S1
100 = Probe S2
MSYFCH
0
0
100
-
I
17
117
R/W
C
/5
Temperature unit of measure: 0 = °C; 1 = °F
MSYFCH
0
0
1
-
D
40
40
R/W
C
/6
Display decimal point: 0/1=no/yes
MSYFCH
0
0
1
-
D
41
41
R/W
C
/tI
Display on user terminal
1
Virtual probe
5
Probe 4
2
Probe 1
6
Reserved
3
Probe 2
7
Set point
4
Probe 3
MSYFCH
1
1
7
-
I
18
118
R/W
C
/tE
Reading on remote display
0
Not fi tted
4
Probe 3
1
Virtual probe
5
Probe 4
2
Probe 1
6
Reserved
4
Probe 3
MSYFCH
0
0
6
-
I
19
119
R/W
C
/P
Type of probe
0 = NTC Standard Range -50T90°C
1 = NTC Enhanced Range -40T150°C
2 = PTC Standard Range -50T150°C
MSYFCH
0
0
2
-
I
20
120
R/W
C
/A2
Probe 2 confi guration (S2)
0
Absent
3
Condenser
1
Product (display only)
4
Frost
2
Defrost
YFCH
MS
2
0
0
0
4
4
-
-
I
l
21
21
121
121
R/W
R/W
C
/A3
Probe 3 confi guration (S3/ DI1)
0
Digital input 1
3
Condenser
1
Product (display only)
4
Frost
2
Defrost
MSYFCH
0
0
4
-
I
22
122
R/W
C
/A4
Probe 4 confi guration (S4/ DI2)
0
Digital input 2
3
Condenser
1
Product (display only)
4
Frost
2
Defrost
MSYFCH
0
0
4
-
I
23
123
R/W
C
/c1
Probe 1 calibration
MSYFCH
0.0
-20
20
-
A
11
11
R/W
C
/c2
Probe 2 calibration
MSYFCH
0.0
-20
20
-
A
12
12
R/W
C
/c3
Probe 3 calibration
MSYFCH
0.0
-20
20
-
A
13
13
R/W
C
/c4
Probe 4 calibration
MSYFCH
0.0
-20
20
-
A
14
14
R/W
User
Par.
Description
Models
Def
Min Max UOM Type CAREL SVP ModBus®
R/W
Ctl
F
St
Set point
MSYFCH
0.0
r1
r2
°C/°F A
16
16
R/W
F
rd
Diff erential
SYFCH
2.0
0.1
20
°C/°F A
17
17
R/W
C
rn
Neutral zone
SYFCH
4.0
0.0
60
°C/°F A
34
34
R/W
C
rr
Reverse diff erential
SYFCH
2.0
0.1
20
°C/°F A
35
35
R/W
C
r1
Minimum set point
MSYFCH
-50
-50
r2
°C/°F A
18
18
R/W
C
r2
Maximum set point
MSYFCH
60
r1
200
°C/°F A
19
19
R/W