9.2 ir33+ wide, ir33+ small wide, easy wide, easy small wide technical specifi cations
Power
supply
Model
Voltage
Power
PBEVxxExxxx
230 V~(+10/-15%), 50/60 Hz 230 V~(+10/-10%), 50/60 Hz (16 A, 8 A, 8 A version)
3 VA, 25mA ~ max
PBEVxxAxxxx
115 V~(+10/-15%), 50/60 Hz 115 V~(+10/-10%), 50/60 Hz (16 A, 8 A, 8 A version)
3 VA, 50mA ~ max
PBEVxxHxxxx
115/230 V~, 50/60 Hz
6 VA, 50mA ~ max
IREVxxLxxxx
12 to 24 V ~, 50/60 Hz, 12/30 Vdc
3 VA, 300 mA ~/ mAdc max
IREVxx0xxxx
12 V ~, 50/60 Hz, 12/18 Vdc
Only use SELV power supply
Insulation guaranteed
by the power supply
IREVxxExxxx
insulation from extra low voltage parts
reinforced, 6 mm clearance, 8 mm creepage, 3750V insulation
IREVxxAxxxxI-
REVxxHxxxx
insulation from relay outputs
basic, 3 mm clearance, 4 mm creepage, 1250V insulation
IREVxxLxxxx
insulation from extra low voltage parts
to be guaranteed externally by safety transformer (SELV)
IREVxx0xxxx
insulation from relay outputs
reinforced, 6 mm clearance, 8 mm creepage, 3750 V insulation
Inputs
S1 (probe 1)
NTC (PBxxx0xxxxx) or NTC and PTC (PBxxx7xxxxx)
S2 (probe 2)
NTC (PBxxx0xxxxx) or NTC and PTC (PBxxx7xxxxx)
DI1
voltage-free contact, contact resistance < 10 Ω, closing current 6 mA
S3
NTC (PBxxx0xxxxx) or NTC and PTC (PBxxx7xxxxx)
DI2
voltage-free contact, contact resistance < 10 Ω, closing current 6 mA
S4
NTC (PBxxx0xxxxx) or NTC and PTC (PBxxx7xxxxx)
Maximum distance between probes and digital inputs less than 10 m
Note
: in the installation it is recommended to separate the power and load connections from the probe, digital input, display and supervisor
cables.
Probe type
Std. Carel NTC
10k
at 25°C, range from –50T90°C
measurement error:
1°C in the range –50T50°C
3°C in the range +50T90°C
High temperature
NTC
50kΩ at 25°C, range –40T150°C
measurement error:
1.5°C in the range –20T115°C
4°C in the range outside of -20T115°C
Standard Carel PTC
985Ω at 25°C, range from -50T150°C
measurement error
2°C in the range from –50T50°C
4°C in the range from +50T150°C
Relay outputs depending on the model
EN60730-1
UL873
Model
relay
250 V~
operating cycles
250 V~
operating
cycles
PBEVxx(E,A)(P,S,V,Y)xxx
5A(*)
5(1) A
100000
5A res. 1FLA 6 LRA C300
30000
PBEVxx(E,A)(N,C,A,L)xxx
PBEVxx(O,H)(N;C;A;L)xxx
8 A(*)
8(4)A N.O. 6(4)A
N.C.2 (2)A N.O./N.C.
100000
8 A res. 2FLA 12 LRA C300
30000
PBEVxx(E,A)(P,S,V,Y)xxx
16 A(*)
10(4)A N.O.(up to
60°C) 12 (2) A
100000
12 A res. 5 FLA 30 LRA C300 30000
2 HP
10(10)A
100000
12 A res. 12 FLA 72 LRA
30000
Insulation from extra low voltage parts
Reinforced, 6 mm clearance, 8 mm creepage, 3750 V insulation
Insulation between independent relay
outputs
Basic, 3 mm clearance, 4 mm creepage, 1250 V insulation
Connections
Cable cross-section from 0.5 to 2.5 mm2 max current 12 A
(*): Relay not suitable for fl uorescent loads (neon lights, etc.) that use starters (ballasts) with phase shifting capacitors. Fluorescent lamps with electronic controllers
or without phase shifting capacitors can be used, depending on the operating limits specifi ed for each type of relay.
The correct sizing of the power and connection cables between the instrument and the loads is the installer’s responsibility. If using the controller at maximum
operating temperature and at full load, the cables used must be suitable for operation at least up to 105 °C.
Clock
error at 25°C ±10 ppm (±5.3 min/year)
error in the range -10T60°C -50 ppm (27 min/year)
Operating temperature
-10T65°C for all versions
Operating humidity
< 90% RH non-condensing
Storage temperature
-20T70°C
Storage humidity
< 90% RH non-condensing
Front panel ingress protection
Assembly on smooth and indeformable panel with gasket: IP65
Environmental pollution
2 (normal situation)
PTI of insulating materials
Printed circuits 250 and insulating materials 175
Period of stress across the insulating parts
long
Heat and fi re resistance category
Category D and category B (UL 94 – V0)
Class of protection against voltage surge
Category II
Type of action and disconnection
1.B relay contacts (microswitching)
Construction of the control device
Built-in, electronic
Classifi cation according to protection against electric shock
Class II when appropriately integrated
Maximum distance between interface and display
10 m
Programming key
Available on all models
Safety standards: compliant with the relevant European standards