38
ENG
ir0300028EN rel. 1.1 - 05.05.2017
User
Par.
Description
Models
Def
Min
Max
UOM Type CAREL SVP ModBus® R/W
ALM
C
A0
Alarm and fan diff erential
MSYFCH
2.0
0.1
20
°C/°F A
26
26
R/W
C
A1
Alarm thresholds (AL, AH) relative to set point or absolute
0/1=relative/absolute
MSYFCH
0
0
1
-
D
48
48
R/W
F
AL
Low temperature alarm threshold
If A1= 0, AL=0: alarm disabled
If A1= 1, AL=-50: alarm disabled
MSYFCH
0.0
-50
200
°C/°F A
27
27
R/W
F
AH
High temperature alarm threshold
If A1= 0, AL=0: alarm disabled
If A1= 1, AL=200: alarm disabled
MSYFCH
0.0
-50
200
°C/°F A
28
28
R/W
F
Ad
High and low temperature alarm delay
MSYFCH
120
0
250
min
I
50
150
R/W
C
A4
Digital input confi guration 1 (DI1)
0 = not active
1 = immediate external alarm
2 = delayed external alarm
3 = select probes (ir33M) / enable defrost
4 = start defrost
5 = door switch with compressor and evaporator fans off
6 = remote ON/OFF
7 = curtain switch
8 = low pressure switch
9 = door switch with fans off
10 = direct/reverse operation
11 = light sensor
12 = activate aux output
13 = door switch with compressor and fans off and light not
managed
14 = door switch with fans off and light not managed
SYFCH
0
0
14
-
I
51
151
R/W
C
A5
Digital input confi guration 2 (DI2)
See A4
MSYFCH
0
0
14
-
I
52
152
R/W
C
A6
Stop compressor on external alarm
0 = compressor always off ;
100 = compressor always on
SYFCH
0
0
100
min
I
53
153
R/W
C
A7
Digital alarm input delay
0 = control outputs unchanged
SYFCH
0
0
250
min
I
54
154
R/W
C
A8
Enable alarms Ed1 and Ed2 (end defrost by timeout)
0 = alarms disabled
SYFCH
0
0
1
-
D
49
49
R/W
C
Ado
Light management with door switch
Ado
Light when ope-
ning the door
Algorithm
Description
0
off
on
Extended normal
Open-close Open-
close-open-close
1
off
on
normal
extended
MSYFCH
0
0
1
-
D
50
50
R/W
C
Ac
High condenser temperature alarm threshold
SYFCH
70.0
0
200
°C/°F A
29
29
R/W
C
AE
High condenser temperature alarm diff erential
SYFCH
10.0
0.1
20
°C/°F A
30
30
R/W
C
Acd
High condenser temperature alarm delay
0 = Immediate alarm
SYFCH
0
0
250
min
I
56
156
R/W
C
AF
Light sensor OFF time
0 = Sensor in the door jamb
> 0 = Sensor inside the cold room or cabinet
SYFCH
0
0
250
s
I
57
157
R/W
C
ALF
Frost protection alarm threshold
MSYFCH
-5.0
-50
200
°C/°F A
36
36
R/W
C
AdF
Frost protection alarm delay
MSYFCH
1
0
15
min
I
136
236
R/W
User
Par.
Description
Models
Def
Min Max UOM Type CAREL SVP ModBus®
R/W
FAn
C
F0
Evaporator fan management
0 = always on
1 = activation based on Sd-Sv (diff erence between virtual probe and
evaporator temperature)
2 = activation based on Sd (evaporator temperature)
FCH
0
0
2
-
I
58
158
R/W
F
F1
Fan activation temperature (only if F0 = 1 or 2)
FCH
5.0
-50
200
°C/°F A
31
31
R/W
C
F2
Evaporator fans with compressor off
0 = See F01 = Always off
FCH
1
0
1
-
D
51
51
R/W
C
F3
Evaporator fans during defrost: 0/1=on/off FCH
1
0
1
-
D
52
52
R/W
F
Fd
Post-dripping time (fans off )
FCH
1
0
15
min I
59
159
R/W
C
F4
Condenser fan deactivation temperature
MSYFCH
40
-50
200
°C/°F A
32
32
R/W
C
F5
Condenser fan activation diff erential
MSYFCH
5.0
0.1
20
°C/°F A
33
33
R/W