37
ENG
ir0300028EN rel. 1.1 - 05.05.2017
C
r3
Operating mode
0 = Direct with defrost control (cooling)
1 = Direct (cooling)
2 = Reverse (heating)
SYFCH
0
0
2
-
I
25
125
R/W
C
r4
Automatic night-time set point variation
MSYFCH
3.0
-20
20
°C/°F A
20
20
R/W
C
r5
Enable temperature monitoring: 0/1=no/yes
MSYFCH
0
0
1
-
D
42
42
R/W
F
rt
Duration of current max and min temperature monitoring session
MSYFCH
0
0
999
hour I
26
126
R
F
rH
Maximum temperature read
MSYFCH
-
-
-
°C/°F A
21
21
R
F
rL
Minimum temperature read
MSYFCH
-
-
-
°C/°F A
22
22
R
User
Par.
Description
Models
Def
Min Max UOM Type CAREL SVP ModBus®
R/W
CMP
C
c0
Compressor, fan and AUX start delay at power on
SYFCH
0
0
15
min I
27
127
R/W
C
c1
Minimum time between successive compressor starts
SYFCH
0
0
15
min I
28
128
R/W
C
c2
Minimum compressor off time
SYFCH
0
0
15
min I
29
129
R/W
C
c3
Minimum compressor on time
SYFCH
0
0
15
min I
30
130
R/W
C
c4
Compressor running time with duty setting
SYFCH
0
0
100
min I
31
131
R/W
C
cc
Continuous cycle duration
SYFCH
0
0
15
hour I
32
132
R/W
C
c6
Low temperature alarm bypass time after continuous cycle
SYFCH
2
0
250
hr/
min
I
33
133
R/W
C
c7
Maximum pump down time (PD)
0 = Pump down disabled
SYFCH
0
0
900
s
I
34
134
R/W
C
c8
Compressor start delay after opening PD valve
SYFCH
5
0
60
s
I
35
135
R/W
C
c9
Autostart in pump down
0 = Disabled
1 = Pump down whenever closing pump down valve & following
low pressure switch activation with no cooling demand
SYFCH
0
0
1
-
D
43
43
R/W
C
c10
Pump down by time or pressure
0/1= pressure/ time
SYFCH
0
0
1
-
D
44
44
R/W
C
c11
Second compressor start delay
SYFCH
4
0
250
s
I
36
136
R/W
User
Par.
Description
Models
Def
Min Max UOM
Type CAREL SVP ModBus®
R/W
dEF
C
d0
Type of defrost
0 = heater by temperature
1 = hot gas by temperature
2 = heater by time (Ed1, Ed2 not shown)
3 = hot gas by time (Ed1, Ed2 not shown)
4 = heater by time with temperature control (Ed1, Ed2 not shown)
SYFCH
0
0
4
-
I
37
137
R/W
F
dI
Maximum time between consecutive defrosts
0 = defrost not performed
SYFCH
8
0
250
hr/min I
38
138
R/W
F
dt1
End defrost temperature probe 2
SYFCH
4
-50
200
°C/°F
A
23
23
R/W
F
dt2
End defrost temperature probe 3 (aux evaporator)
SYFCH
4
-50
200
°C/°F
A
24
24
R/W
F
dt3
End defrost temperature probe 4
SYFCH
4
-50
200
°C/°F
A
38
38
R/W
F
dP1
Maximum defrost duration
SYFCH
30
1
250
min/s I
39
139
R/W
F
dP2
Maximum aux evaporator defrost duration
SYFCH
30
1
250
min/s I
40
140
R/W
C
d3
Defrost activation delay
SYFCH
0
0
250
min
I
41
141
R/W
C
d4
Defrost at start-up: 0/1=disabled/enabled
SYFCH
0
0
1
fl ag
D
45
45
R/W
C
d5
Defrost delay at start-up (if d4=1) or from dI
SYFCH
0
0
250
min
I
42
142
R/W
C
d6
Terminal display during defrost
0 = Temperature alternating with dEF
1 = Display disabled
2 = dEF
SYFCH
1
0
2
-
I
43
143
R/W
F
dd
Dripping time after defrost (fans off )
SYFCH
2
0
15
min
I
44
144
R/W
F
d8
High temperature alarm bypass time after defrost (and door open)
SYFCH
1
0
250
hr/min I
45
145
R/W
C
d8d
Alarm bypass time after door open
SYFCH
0
0
250
min
I
139
239
R/W
C
d9
Defrost priority over compressor protectors
0/1 = yes/no
SYFCH
0
0
1
-
D
46
46
R/W
F
d/1
Display defrost probe 1
MSYFCH
-
-
-
°C/°F
A
1
1
R
F
d/2
Display defrost probe 2
MSYFCH
-
-
-
°C/°F
A
2
2
R
C
dC
Time base for defrost
0 = dI in hours, dP 1 and dP2 in minutes
1 = dI in minutes, dP1 and dP2 in seconds
SYFCH
0
0
1
-
D
47
47
R/W
C
dC1
Time base for c6 and d8: 0/1 = hours/minutes
SYFCH
0
0
1
-
D
65
65
R/W
C
d10
Defrost time in “Running time” mode0 = function disabled
SYFCH
0
0
250
hour
I
46
146
R/W
C
d11
Running time defrost temperature threshold
SYFCH
1.0
-20
20
°C/°F
A
25
25
R/W
C
d12
Advanced defrosts
d12
Skip defrost
Automatic variation of dI
0
Disabled
Disabled
1
Disabled
Enabled
2
Enabled
Disabled
3
Enabled
Enabled
SYFCH
0
0
3
-
I
47
147
R/W
C
dn
Nominal defrost duration
SYFCH
65
1
100
-
I
48
148
R/W
C
dH
Proportional factor for variation of dI
SYFCH
50
0
100
-
I
49
149
R/W
Содержание easy small wide