9. TECHNICAL 

SPECIFICATIONS

9.1  ir33+ technical specifi cations

Power supply

Model

Voltage

Power

IREVxxExxxx

230 V~, 50/60 Hz

3 VA, 25mA ~ max

IREVxxAxxxx

115 V~, 50/60 Hz

3 VA, 50mA ~ max

IREVxxHxxxx

115/230 V~, 50/60 Hz

6 VA, 50mA ~ max

IREVxxLxxxx

12 to 24 V ~, 50/60 Hz, 12/30 Vdc

3 VA, 300 mA ~/ mAdc max

IREVxx0xxxx

12 V ~, 50/60 Hz, 12/18 Vdc

Only use SELV power supply

Insulation guaranteed 
by the power supply

IREVxxExxxx 
IREVxxAxxxx

insulation from extra low voltage parts

reinforced, 6 mm clearance, 8 mm creepage, 3750V insulation

IREVxxHxxxx

insulation from relay outputs

basic, 3 mm clearance, 4 mm creepage, 1250V insulation

IREVxxLxxxx 

insulation from extra low voltage parts

to be guaranteed externally by safety transformer (SELV)

IREVxx0xxxx

insulation from relay outputs

reinforced, 6 mm clearance, 8 mm creepage, 3750 V insulation

Inputs

S1 (probe 1)

NTC (IRxxx0xxxxx) or NTC and PTC (IRxxx7xxxxx)

S2 (probe 2)

NTC (IRxxx0xxxxx) or NTC and PTC (IRxxx7xxxxx)

DI1

voltage-free contact, contact resistance < 10 

, closing current 6 mA

S3

NTC (IRxxx0xxxxx) or NTC and PTC (IRxxx7xxxxx)

DI2

voltage-free contact, contact resistance < 10 

, closing current 6 mA

S4

NTC (IRxxx0xxxxx) or NTC and PTC (IRxxx7xxxxx)

Maximum distance between probes and digital inputs less than 10 m

Note: 

in the installation it is recommended to separate the power and load connections from the probe, digital input, display and supervi-

sor cables.

Probe type

Std. Carel NTC

10k 



at 25°C, range from –50T90°C

measurement error:

1°C in the range –50T50°C
3°C in the range +50T90°C

High temperature 
NTC

50k

 at 25°C, range –40T150°C

measurement error:

1.5°C in the range –20T115°C
4°C in the range outside of -20T115°C

Standard Carel PTC

985

 at 25°C, range from -50T150°C

measurement error

2°C in the range from –50T50°C4°C in the range from +50T150°C

Relay 
outputs

depending on the model

EN60730-1

UL 873

model

relay

250 V~

operating cycles 250 V~

operating cycles

IRxxxx(E,A)(P,Q,S,U,V,X,Y,Z)xxx

R2(*)

5 (1) A

100000

5 A res 1 FLA 
6 LRA C300

30000

IRxxxx(E,A)(N, R, C, B,A,M,L, T)xxx

R3(*)

5 (1) A

100000

5 A res 1 FLA 
6 LRA C300

30000

IRxxxx(E,A)(N, R, C, B, A, M, L, T)xxx

R1, R2

8 (4)A N.O. 6(4) A N.C. 100000

8 A res 2 FLA

30000

IRxxxx(0, L, H)(N, R, C, B, A, M, L, T)xxx

R2, R3, R4 (*)

2(2) A N.O./N.C.

12 LRA C300

IRxxxx(E,A)(P, Q, S, U, V, X, Y, Z)xxx

R1

12 (2)A N.O./ N.C.

100000

12 A res 5 FLA

30000

IRxxxx(0, L, H)(N, R, C, B, A, M, L, T)xxx

R1

12 (2)A N.O./ N.C.

100000

30 LRA C300

insulation from extra low voltage parts

reinforced, 6 mm clearance, 8 mm creepage, 3750 V insulation

insulation between independent relay outputs

basic, 3 mm clearance, 4 mm creepage, 1250 V insulation

SSR outputs Max output voltage 12 Vdc

Output resistance 600 

Max output current 20 mA

Connections Cable cross-section from 0.5 to 2.5 mm2 max current 12 A
(*): Relay not suitable for fl uorescent loads (neon lights, etc.) that use starters (ballasts) with phase shifting capacitors. Fluorescent lamps with electronic controllers 
or without phase shifting capacitors can be used, depending on the operating limits specifi ed for each type of relay.
The correct sizing of the power and connection cables between the instrument and the loads is the installer’s responsibility. Depending on the model, the maxi-
mum current at common terminals 1, 3 or 5 is 12 A. If using the controller at maximum operating temperature and at full load, the cables used must be suitable for 
operation at least up to 105 °C.

Clock

error at 25° C ±10 ppm (±5 min/year)
error at 25° C -10T60 °C -50 ppm (27 min/year)

Operating temperature

-10T60 °C for all versions

Operating humidity

< 90% RH non-condensing

Front panel ingress protection

assembly on smooth and indeformable panel with IP65 gasket

Environmental pollution

2 (normal situation)

PTI of insulating materials

printed circuits 250, plastic and insulating materials 175

Period of stress across the insulating parts

long

Heat and fi re resistance category

category D and category B (UL 94-V0)

Class of protection against voltage surge

category II

Type of action and disconnection

1.B relay contacts (microswitching)

Construction of the control device

built-in, electronic

Classifi cation according to protection against electric shock

class II when appropriately integrated

Maximum distance between interface and display

10 m

Programming key

available on all models

Safety standards

compliant with relevant European standards

Tab. 9.a

Содержание easy small wide

Страница 1: ...I n t e g r a t e d C o n t r o l S o l u t i o n s E n e r g y S a v i n g s ir33 platform ir33 ir33 wide ir33 small wide easy wide y easy small wide Electronic controller User manual...

Страница 2: ......

Страница 3: ...ot use corrosive chemicals solvents or aggressive detergents to clean the device Do not use the product for applications other than those specified in the technical manual All of the above suggestions...

Страница 4: ...4 ENG ir33plus 0300028EN rel 1 1 05 05 2017...

Страница 5: ...ter 31 6 8 Light and Aux outputs 32 6 9 Defrost 32 6 10 Evaporator fans 34 6 11 Condenser fans 35 6 12 Duty setting par c4 35 6 13 Running time defrost par d10 d11 35 7 PARAMETER TABLE 36 7 14 Variabl...

Страница 6: ...6 ENG ir33plus 0300028EN rel 1 1 05 05 2017...

Страница 7: ...by different icons according to the category temperature control with virtual control probe and set point variation at night digital inputs to activate alarms enable or activate defrosts door curtain...

Страница 8: ...nstruction sheet 050003920 IREVXGD000 PST00VR100 Fig 1 g Fig 1 h RS485 serial interface P N IROPZ48500 and IROPZ485S0 Plugged directly into the programming key connector this provides connection to th...

Страница 9: ...Fig 2 e 2 2 Panel mounting To install the ir33 ir33 wide and ir33 small wide controllers use the 2 brackets shown in the figure 1 2 Fig 2 f 2 3 Rear panel mounting The models with separate membrane k...

Страница 10: ...o ir33 165 mm 21 mm 55 mm 26 1 mm Fig 2 j easy wide easy small wide STEP 1 Apply the two covered brackets to the controller Drill the holes with the spacing shown in the figure and make the opening fo...

Страница 11: ...xAxxxx 115 V 50 mA max SERIAL and KEY Fig 2 t 6 7 8 4 A 8A 2FLA 12LRA 1 2 3 4 5 8 9 10 11 12 PROBES DI DI L N 1 2 1 2 R1 R2 R1 R2 12 2 A 12A 5FLA 30LRA EN60730 1 UL 873 AUX 10T60 POWER SUPPLY 250 V Co...

Страница 12: ...on terminal 3 12 A Ixxxxx0xxxx 12 V 300 mA max 12 18 Vdc 300 mA dc max IxxxxxLxxxx 12 24 V 300 mA max 12 30 Vdc 300 mA dc max tLAN interface SERIAL and KEY IxxxF 0 7 0 L N C 0 2 xx Fig 2 ac 6 7 tLAN...

Страница 13: ...Corrente massima totale su terminale 3 12 A Maximum current on terminal 3 12 A L N 115 230 V 50 mA max tLAN interface SERIAL and KEY IxxxC 0 7 H N C 0 2 xx Fig 2 ad 6 7 8 4 A 8A 2FLA 12LRA 8 4 A 8A 2F...

Страница 14: ...o not use ethanol hydrocarbons petrol ammonia and by products Use neutral detergents and water 2 9 Programming key copy set up Programming key IROPZKEY00 A0 The programming key can load up to 7 differ...

Страница 15: ...g the settings of the dipswitches on the key 1 open the rear cover on the key and position the 2 dipswitches according to the desired operation 2 close the rear cover on the key and plug the key into...

Страница 16: ...s of the parameters The remote display IREVXGD000 PST00VR100 shows the temperature with resolution to the tenths between 9 9 C and19 9 C Note the standard display on the user terminal and the remote d...

Страница 17: ...he continuous cycle AUX DOWN SET DEF if pressed together for more than 1 second displays a submenu used to access the HACCP alarm parameters SET DEF If pressed for more than 1 s displays and or lets t...

Страница 18: ...the set point differential temperature monitoring interval interval between defrosts end defrost temperature dripping time alarm thresholds alarm bypass times etc See the parameter table Procedure 1 p...

Страница 19: ...P DOWN button for at least 5 seconds all the changes made to the parameters temporarily stored in the RAM can be cancelled by not pressing any button for 60 seconds thus returning to the standard disp...

Страница 20: ...st deactivation on ir33 On Off To switch the controller off from the keypad press On Off for 3 seconds The display shows the text Off flashing for 3 seconds and then on steady Finally the text Off alt...

Страница 21: ...inally press Prg for 5 seconds to save the value of the parameter HACCP menu The controller must be fitted with the RTC real time clock To enter the HACCP menu press the combination button shown the t...

Страница 22: ...ple in the case of bottle coolers typically used in supermarkets where the doors are opened frequently due to the greater thermal inertia of the liquids compared to the air and the fact that the probe...

Страница 23: ...ogramming key Procedure power down the controller power up while holding Prg mute the display will show the first set bn0 press UP DOWN to select set bn1 to bn6 For example select bn2 press Set to con...

Страница 24: ...reasing order with that configuration Par Description Def Min Max UOM A2 Probe 2 configuration S2 M models 0 0 4 A2 Probe 2 configuration S2 0 Absent 1 Product display only 2 Defrost 3 Condenser 4 Fro...

Страница 25: ...delayed external alarm is thus signal only 3 Probe shown on the display IR33M models On thermometer only models this setting selection is used to exploit the digital input in order to show on the disp...

Страница 26: ...close the door If after being closed for the first time the door remains closed for longer than time d8 or d8d the controller resumes normal operation compressor and evaporator fan switched on if nee...

Страница 27: ...r3 direct reverse operating mode When the contact is open the controller operates in direct mode cooling when the contact is closed in reverse mode heating A switch can therefore be connected to sele...

Страница 28: ...when the internal timer is set Relay output protectors parameters c7 c8 c9 Par Description Def Min Max UOM c0 Compressor fan and AUX start delay at power on 0 0 15 min c1 Minimum time between success...

Страница 29: ...r4 Automatic night time set point variation 3 0 20 20 C F 4 Virtual probe composition 0 control probe S1 100 probe S2 0 0 100 Tab 6 b Parameter 4 is used to determine the virtual probe Sv as the weigh...

Страница 30: ...wn whenever closing pump down valve following low pressure switch activation with no cooling demand c10 Pump down by time or pressure 0 1 pressure time 0 0 1 Tab 6 d Note c8 is a masked parameter and...

Страница 31: ...alarm signal can be ignored by suitably setting parameter c6 alarm bypass after continuous cycle Par Description Def Min Max UOM cc Continuous cycle duration 0 0 15 hour c6 Low temperature alarm bypa...

Страница 32: ...me 4 heater by time with temperature control The defrost can end by temperature in which case the defrost probe Sd must be installed or by time In the first case the defrost ends when the defrost prob...

Страница 33: ...valve Pump down Pump down stage FAN Evaporator fan Def Defrost V_def Hot gas valve Drip Dripping E Evaporator Post drip Post dripping C Condenser S2 Defrost probe V2 Thermostatic expansion valve L Li...

Страница 34: ...situation of this type it is preferable to enable defrost on start up above all if the defrost is controlled by temperature probe on the evaporator therefore avoiding unnecessary defrosts or at least...

Страница 35: ...20 C F Tab 6 o ON OFF FAN F4 F5 Sc F4 F4 0 2 First switch on t t Fig 6 t Key Sc Condenser probe Sv Virtual probe FAN Condenser fans t Time F4 Deactivation temperature F5 Differential Note if no conde...

Страница 36: ...irtual probe 5 Probe 4 2 Probe 1 6 Reserved 4 Probe 3 MSYFCH 0 0 6 I 19 119 R W C P Type of probe 0 NTC Standard Range 50T90 C 1 NTC Enhanced Range 40T150 C 2 PTC Standard Range 50T150 C MSYFCH 0 0 2...

Страница 37: ...shown 4 heater by time with temperature control Ed1 Ed2 not shown SYFCH 0 0 4 I 37 137 R W F dI Maximum time between consecutive defrosts 0 defrost not performed SYFCH 8 0 250 hr min I 38 138 R W F dt...

Страница 38: ...ed SYFCH 0 0 250 min I 54 154 R W C A8 Enable alarms Ed1 and Ed2 end defrost by timeout 0 alarms disabled SYFCH 0 0 1 D 49 49 R W C Ado Light management with door switch Ado Light when ope ning the do...

Страница 39: ...sweat heater function disabled F MSYFCH 0 50 200 C F A 37 37 R W C HrL Remote light relay status on Master 0 disabled MSYFCH 0 0 1 D 62 62 R W C HrA Remote AUX relay status on Master 0 disabled MSYFCH...

Страница 40: ...of parameter sets available I 137 237 R Digital input 1 status D 6 6 R Digital input 2 status D 7 7 R Virtual probe fault alarm D 9 9 R Probe alarm 1 D 10 10 R Probe alarm 2 D 11 11 R Probe alarm 3 D...

Страница 41: ...controller itself on the probes or in network communication An alarm can also be activated from an external contact immediate or delayed See paragraph 5 2 The display shows IA or dA and at the same t...

Страница 42: ...year month day hours minutes and duration in minutes of the selected alarm press Prg mute again to return to the previous list In addition the HACCP alarm menu allows the following operations delete t...

Страница 43: ...nal contact ON ON automatic duty setting A6 duty setting A6 OFF OFF OFF duty setting A6 dA Delayed alarm from external contact ON ON automatic duty setting A6 OFF if A7 0 OFF if A7 0 OFF if A7 0 duty...

Страница 44: ...old or the contact closes the alarm is not signalled and the count is reset When a new alarm condition occurs the count starts from 0 again Parameter A6 has a similar meaning to parameter c4 duty sett...

Страница 45: ...erature alarm threshold Acd Alarm delay cht High cond temperature pre alarm Sc Condenser probe CHT High condensing temperature alarm AE High condensing temperature alarm differential 8 8 Frost protect...

Страница 46: ...1 FLA 6 LRA C300 30000 IRxxxx E A N R C B A M L T xxx R1 R2 8 4 A N O 6 4 A N C 100000 8 A res 2 FLA 30000 IRxxxx 0 L H N R C B A M L T xxx R2 R3 R4 2 2 A N O N C 12 LRA C300 IRxxxx E A P Q S U V X Y...

Страница 47: ...ing cycles 250 V operating cycles PBEVxx E A P S V Y xxx 5A 5 1 A 100000 5A res 1FLA 6 LRA C300 30000 PBEVxx E A N C A L xxx PBEVxx O H N C A L xxx 8 A 8 4 A N O 6 4 A N C 2 2 A N O N C 100000 8 A res...

Страница 48: ...5A on model IRYS0EP 8 A Programming keypad key Special functions HACCP Real Time Clock Function can be enabled when Real Time Clock option available models IR C B L T S U Y Z and on IR33 power models...

Страница 49: ...twork interface Note standard Tab 9 e 9 6 easy wide part numbers Features PBEVS0EAAA PBEVY0EVD0 PBEVC0HND0 PBEVC0HNBA PBEVC0HCAA PBEVH0HNAA PBEVH0HNB0 PBEVH0HNBW PBEVS0SAFA PBEVC0SNFA PBEVC0SNFW Power...

Страница 50: ...PZKEYA0 connected to the computer via the converter IROPZPRG00 When opening the VPM program choose the device to be configured ir33 The Home page is displayed with the options to create a new project...

Страница 51: ...he right button choose Add set for each additional set Fig 10 i Set1 is displayed Fig 10 j Note onthecontroller Set0 Set1 Set6arenamedbn0tobn6respectively Set0 is the default set on the controller i e...

Страница 52: ...d starting from the eighth defrost Note if there are two evaporators the defrost duration used to determine the defrosts to be skipped is the longer nominal defrost duration Possible operating sequenc...

Страница 53: ...2 The following situations may occur if the outputs are not configured or there are probe alarms DEFROST BY TEMPERATURE Defrost probe evap output config Situation Effect Probe 2 defrost output 1 No pr...

Страница 54: ...of operation ON OFF REQ2 CP1 CP2 REQ1 ON OFF ON OFF OFF ON EXAMPLE 1 t t t t Fig 11 d ON OFF REQ2 CP1 CP2 REQ1 ON OFF ON OFF OFF ON EXAMPLE 2 t t t t Fig 11 e ON OFF REQ2 CP1 CP2 REQ1 ON OFF ON OFF OF...

Страница 55: ......

Страница 56: ...EL INDUSTRIES Headquarters Via dell Industria 11 35020 Brugine Padova Italy Tel 39 049 9716611 Fax 39 049 9716600 e mail carel carel com www carel com Agenzia Agency ir33plus 0300028EN rel 1 1 05 05 2...

Отзывы: