27
ENG
ir0300028EN rel. 1.1 - 05.05.2017
Key
St
Set point
rd
Diff erential
CMP
Compressor
FAN
Fan
Sv
Virtual probe
r4
Automatic night-time set point variation
Note:
if one of the auxiliary outputs is used to manage the light,
lowering the curtain automatically switches the light off , while raising it
switches the light on.
8 = Low pressure switch input for pump down
See par. 6.4. Setting “A4”=8 manages the low pressure switch. The low
pressure alarm “LP” is signalled when the low pressure switch is activated:
•
during normal control (c7=0) with the compressor on, or alternatively
•
with pump-down function confi gured (c7 >0), if the pump down valve
is open and the compressor is on.
The low pressure alarm signal is delayed by the time set for parameter
“A7”. The low pressure alarm “LP” stops the compressor.
ir33+
ON
OFF
ON
OFF
t
CMP
LOW
Pressure
switch
Pump down
valve
HIGH
OFF
ON
LP
Alarm
A7
Fig. 5.e
Key
CMP
Compressor
Pump down valve Pump down valve
Pressure Switch Pressure
switch
LP alarm
Low pressure alarm
t
Time
A7
Alarm signal delay
Note:
this parameter, together with c7, c8, c9 and H1, H5, allows
management of the “pump-down” algorithm (see par 6.3).
9 = Door switch with fan off only
Same as for option “A4”=5, with the diff erence being that when opening
the door only the evaporator fan is switched off .
10 = Direct/reverse operation
Important:
when A4 = 10, the status of digital input has priority
over the setting of parameter r3 (direct/reverse operating mode).
When the contact is open, the controller operates in “direct” mode
(cooling), when the contact is closed, in “reverse” mode (heating). A switch
can therefore be connected to select heating or cooling operation.
St
Sv
rd
OFF
ON
DI OPEN
CMP/FAN
r3 = 0, 1, 2
DIRECT
Sv
rd
OFF
ON
DI CLOSED
CMP/FAN
r3 = 0, 1, 2
REVERSE
St
Fig. 5.f
Key
St
Set point
Sv
Virtual probe
rd
Diff erential
CMP
Compressor
FAN
Fan
11 = Light sensor
The digital input is used to read a light sensor (P/N PSOPZLHT00, actually an
analogue input, from which a digital signal is taken using the parameter or
threshold of the light sensor).
The light sensor can be located:
•
in the door jamb (ref. A);
•
inside the cold room or cabinet (ref. B).
Par. Description
Def
Min Max UOM
AF
Light sensor OFF time
0 Sensor in the door jamb
> 0 Sensor inside the cold room or cabinet
0
0
250
s
Tab. 5.h
B
A
Fig. 5.g
A (AF=0)
B (AF = 1)
Light sensor
signal
The sensor signals
the opening and
closing of the door
The sensor signals the opening of the
door and detects light inside the cabi-
net/cold room. The sensor also signals
closing of the door
Inside light: on With the door open If the sensor detects light
Inside light: off With the door
closed, minimum off
time of 5 s, to avoid
rapid, successive
impulses of the light
relay
Closing of the door is measured by
time, as the inside light will illuminate
the sensor. After the time AF (>0) the
inside light is switched off for 5 secon-
ds. If the light sensor signals darkness,
the door must be closed and the light
will therefore remain off ;
if it signals light: the door is open and
the light will be switched on again.
Tab. 5.i