25
ENG
ir0300028EN rel. 1.1 - 05.05.2017
The following parameters are involved in the explanation of the settings
for A4 and A5.
Par. Description
Def
Min Max UOM
A4
Multifunction digital input 1 confi guration
(DI1)
See the previous table
0/3
(IR33M)
0
14
-
A5
Multifunction digital input 2 confi guration
(DI2)
See the previous table
0
0
14
-
A6
Stop compressor on external alarm
0 = compressor always off ;
100 = compressor always on
0
0
100
min
A7
Digital alarm input delay0 = control
outputs unchanged
0
0
250
min
Ado Light management with door switch
0
0
1
-
c7
Maximum pump down time (PD)
0 = Pump down disabled
0
0
900
s
d5
Defrost delay at start-up (if d4=1) or from
DI
0
0
250
min
d8
High temperature alarm bypass time after
defrost (and door open)
1
0
250
hr/
min
d8d Alarm bypass time after door open
0
0
250
min
dI
Maximum time between consecutive
defrosts - 0 = defrost not performed
8
0
250
hr/
min
Tab. 5.e
1 = Immediate external alarm
Application: external alarm that requires immediate action (for example
high pressure alarm or compressor thermal overload). When the alarm is
activated:
1.
the following actions occur:
•
a signal is shown on the display (‘IA’);
•
the icon
fl ashes;
•
the buzzer is activated, if enabled;
•
the alarm relay is activated, if selected;
2.
and the actuators behave as follows:
•
compressor: operates depending on the values assigned to
parameter ‘A6’ (stop compressor on external alarm).
•
fans: continue operating according to the fan parameters (“F”).
Note
when the compressor stops, the minimum compressor on
time (“c3”) is ignored.
2 = Delayed external alarm
The delayed external alarm is equivalent to the immediate external alarm,
however with the addition of a delay A7 before the signal (“dA”).
Application: this confi guration is especially useful for managing the low
pressure alarm. In fact, when starting for the fi rst time, the unit often
detects a low pressure alarm due to the environmental conditions rather
than a unit malfunction. Setting a delay for the alarm (par. A7) will avoid
false signals. In fact, by suitably calculating the delay, if the low pressure
is due to environmental conditions (low temperature), the alarm will be
automatically reset before the delay has elapsed.
Note
if “A7”=0 activation of the alarm does not cause the compressor
to operate according to the values assigned to parameter ‘A6’ (stop
compressor on external alarm); on the other hand, the “dA” signal is
displayed, the icon
fl ashes, the buzzer and the alarm relay (if selected)
are activated; the delayed external alarm is thus signal-only.
3 = Probe shown on the display (IR33M models)
On thermometer-only models, this setting selection is used to exploit
the digital input in order to show, on the display, the probe selected by
parameter “/tI” or the fi rst enabled probe (see parameters “/A2”,”/A3”,”/A4”).
In practice, if the contact is open, the probe selected by parameter “/tI” is
shown, whereas, if the contact is closed, the fi rst enabled probe is shown.
Note:
if more than one digital input is confi gured as the probe
selection, the probe selected by parameter /tI is displayed when at least
one of the inputs is open.
3 = Enable defrost (all other models)
Application: any defrosts called when the contact is open remain pending
until the contact closes. The various possibilities are shown below.
A4 = 3
Contact
Defrost
Open
Not enabled
Closed
Enabled
Closed without
request from the
controller
Not performed
Closed with in
progress
When the digital input opens, the defrost is immedia-
tely stopped and the unit restarts normal operation
(without performing the dripping or post-dripping
stages). The
LED starts fl ashing to indicate that the
defrost call is pending, awaiting the next enabling
signal (closing of the contact), when the defrost will
be performed completely.
Tab. 5.f
Note
this function is useful to prevent defrosts on units accessible to
the public during opening times.
4 = Start defrost from external contact
Application: this function is useful for performing defrosts in real time. To
perform the defrosts, connect a cyclical, mechanical or electronic timer
to the selected digital input: a series of units can be connected to the
same timer, setting diff erent values for parameter d5 (defrost delay from
multifunction input) to avoid simultaneous defrosts.
Important:
for 12 Vac and 12/24 Vac versions. When connecting a
series of units to the same timer, the best solution is to insulate all the
contacts galvanically, inserting an intermediate relay for each contact.
ON
OFF
ON
OFF
OFF
t
TIMER
OFF
dP(2)
dP(1)
d5(2)
DEFROST
UNIT 1
UNIT 2
UNIT 3
DEFROST
ON
ON
OFF
ON
DEFROST
dP(3)
d5(1)=0
d5(3)
Fig. 5.b
Key
dP
Maximum defrost duration
d5 Defrost delay from
digital input
UNIT 1…3
Unit 1-3
t
Time
5 = Door switch with compressor and evaporator fan off
Parameter d8 defi nes the high temperature alarm bypass time after the
defrost ends (or the door is opened).
Parameter d8d is the alarm bypass time after the door is opened. If d8d=0,
the alarm delay after door open coincides with the value of parameter d8.
Setting “A4”=5 manages the cold room door switch. The behaviour of the
door switch depends on the status of the light when the door is opened:
1.
light off ;
2.
light on.