25

ENG

ir0300028EN rel. 1.1 - 05.05.2017

The following parameters are involved in the explanation of the settings 
for A4 and A5.

Par. Description

Def

Min Max UOM

A4

Multifunction digital input 1 confi guration 
(DI1)
See the previous table

0/3 
(IR33M)

0

14

-

A5

Multifunction digital input 2 confi guration 
(DI2)
See the previous table

0

0

14

-

A6

Stop compressor on external alarm
0 = compressor always off ;
100 = compressor always on

0

0

100

min

A7

Digital alarm input delay0 = control 
outputs unchanged

0

0

250

min

Ado Light management with door switch

0

0

1

-

c7

Maximum pump down time (PD)
0 = Pump down disabled

0

0

900

s

d5

Defrost delay at start-up (if d4=1) or from 
DI

0

0

250

min

d8

High temperature alarm bypass time after 
defrost (and door open)

1

0

250

hr/
min

d8d Alarm bypass time after door open

0

0

250

min

dI

Maximum time between consecutive 
defrosts  -  0 = defrost not performed

8

0

250

hr/
min

Tab. 5.e 

1 = Immediate external alarm

Application: external alarm that requires immediate action (for example 
high pressure alarm or compressor thermal overload). When the alarm is 
activated:

1. 

the following actions occur:

• 

a signal is shown on the display (‘IA’);

• 

the icon 

 fl ashes;

• 

the buzzer is activated, if enabled;

• 

the alarm relay is activated, if selected;

2. 

and the actuators behave as follows:

• 

compressor: operates depending on the values assigned to 
parameter ‘A6’ (stop compressor on external alarm).

• 

fans: continue operating according to the fan parameters (“F”).

Note

 when the compressor stops, the minimum compressor on 

time (“c3”) is ignored.

2 = Delayed external alarm

The delayed external alarm is equivalent to the immediate external alarm, 
however with the addition of a delay A7 before the signal (“dA”).

Application: this confi guration is especially useful for managing the low 
pressure alarm. In fact, when starting for the fi rst time, the unit often 
detects a low pressure alarm due to the environmental conditions rather 
than a unit malfunction. Setting a delay for the alarm (par. A7) will avoid 
false signals. In fact, by suitably calculating the delay, if the low pressure 
is due to environmental conditions (low temperature), the alarm will be 
automatically reset before the delay has elapsed.

Note

 if “A7”=0 activation of the alarm does not cause the compressor 

to operate according to the values assigned to parameter ‘A6’ (stop 
compressor on external alarm); on the other hand, the “dA” signal is 

displayed, the icon 

 fl ashes, the buzzer and the alarm relay (if selected) 

are activated; the delayed external alarm is thus signal-only.

3 = Probe shown on the display (IR33M models)

On thermometer-only models, this setting selection is used to exploit 
the digital input in order to show, on the display, the probe selected by 
parameter “/tI” or the fi rst enabled probe (see parameters “/A2”,”/A3”,”/A4”). 
In practice, if the contact is open, the probe selected by parameter “/tI” is 
shown, whereas, if the contact is closed, the fi rst enabled probe is shown.

Note:

 if more than one digital input is confi gured as the probe 

selection, the probe selected by parameter /tI is displayed when at least 
one of the inputs is open.

3 = Enable defrost (all other models)

Application: any defrosts called when the contact is open remain pending 
until the contact closes. The various possibilities are shown below. 

A4 = 3
Contact

Defrost

Open

Not enabled

Closed

Enabled

Closed without 
request from the 
controller

Not performed

Closed with in 
progress

When the digital input opens, the defrost is immedia-
tely stopped and the unit restarts normal operation 
(without performing the dripping or post-dripping 
stages). The 

 LED starts fl ashing to indicate that the 

defrost call is pending, awaiting the next enabling 
signal (closing of the contact), when the defrost will 
be performed completely.

Tab. 5.f

Note

 this function is useful to prevent defrosts on units accessible to 

the public during opening times.

4 = Start defrost from external contact 

Application: this function is useful for performing defrosts in real time. To 
perform the defrosts, connect a cyclical, mechanical or electronic timer 
to the selected digital input: a series of units can be connected to the 
same timer, setting diff erent values for parameter d5 (defrost delay from 
multifunction input) to avoid simultaneous defrosts.

Important: 

for 12 Vac and 12/24 Vac versions. When connecting a 

series of units to the same timer, the best solution is to insulate all the 
contacts galvanically, inserting an intermediate relay for each contact.

ON

OFF

ON

OFF

OFF

t

TIMER

OFF

dP(2)

dP(1)

d5(2)

DEFROST

UNIT 1

UNIT 2

UNIT 3

DEFROST

ON

ON

OFF

ON

DEFROST

dP(3)

d5(1)=0

d5(3)

Fig. 5.b

Key

dP

Maximum defrost duration

d5  Defrost delay from 

digital input

UNIT 1…3

Unit 1-3

t

Time

5 = Door switch with compressor and evaporator fan off 

Parameter d8 defi nes the high temperature alarm bypass time after the 
defrost ends (or the door is opened).

Parameter d8d is the alarm bypass time after the door is opened. If d8d=0, 
the alarm delay after door open coincides with the value of parameter d8.
Setting “A4”=5 manages the cold room door switch. The behaviour of the 
door switch depends on the status of the light when the door is opened:

1. 

light off ;

2. 

light on.

Содержание easy small wide

Страница 1: ...I n t e g r a t e d C o n t r o l S o l u t i o n s E n e r g y S a v i n g s ir33 platform ir33 ir33 wide ir33 small wide easy wide y easy small wide Electronic controller User manual...

Страница 2: ......

Страница 3: ...ot use corrosive chemicals solvents or aggressive detergents to clean the device Do not use the product for applications other than those specified in the technical manual All of the above suggestions...

Страница 4: ...4 ENG ir33plus 0300028EN rel 1 1 05 05 2017...

Страница 5: ...ter 31 6 8 Light and Aux outputs 32 6 9 Defrost 32 6 10 Evaporator fans 34 6 11 Condenser fans 35 6 12 Duty setting par c4 35 6 13 Running time defrost par d10 d11 35 7 PARAMETER TABLE 36 7 14 Variabl...

Страница 6: ...6 ENG ir33plus 0300028EN rel 1 1 05 05 2017...

Страница 7: ...by different icons according to the category temperature control with virtual control probe and set point variation at night digital inputs to activate alarms enable or activate defrosts door curtain...

Страница 8: ...nstruction sheet 050003920 IREVXGD000 PST00VR100 Fig 1 g Fig 1 h RS485 serial interface P N IROPZ48500 and IROPZ485S0 Plugged directly into the programming key connector this provides connection to th...

Страница 9: ...Fig 2 e 2 2 Panel mounting To install the ir33 ir33 wide and ir33 small wide controllers use the 2 brackets shown in the figure 1 2 Fig 2 f 2 3 Rear panel mounting The models with separate membrane k...

Страница 10: ...o ir33 165 mm 21 mm 55 mm 26 1 mm Fig 2 j easy wide easy small wide STEP 1 Apply the two covered brackets to the controller Drill the holes with the spacing shown in the figure and make the opening fo...

Страница 11: ...xAxxxx 115 V 50 mA max SERIAL and KEY Fig 2 t 6 7 8 4 A 8A 2FLA 12LRA 1 2 3 4 5 8 9 10 11 12 PROBES DI DI L N 1 2 1 2 R1 R2 R1 R2 12 2 A 12A 5FLA 30LRA EN60730 1 UL 873 AUX 10T60 POWER SUPPLY 250 V Co...

Страница 12: ...on terminal 3 12 A Ixxxxx0xxxx 12 V 300 mA max 12 18 Vdc 300 mA dc max IxxxxxLxxxx 12 24 V 300 mA max 12 30 Vdc 300 mA dc max tLAN interface SERIAL and KEY IxxxF 0 7 0 L N C 0 2 xx Fig 2 ac 6 7 tLAN...

Страница 13: ...Corrente massima totale su terminale 3 12 A Maximum current on terminal 3 12 A L N 115 230 V 50 mA max tLAN interface SERIAL and KEY IxxxC 0 7 H N C 0 2 xx Fig 2 ad 6 7 8 4 A 8A 2FLA 12LRA 8 4 A 8A 2F...

Страница 14: ...o not use ethanol hydrocarbons petrol ammonia and by products Use neutral detergents and water 2 9 Programming key copy set up Programming key IROPZKEY00 A0 The programming key can load up to 7 differ...

Страница 15: ...g the settings of the dipswitches on the key 1 open the rear cover on the key and position the 2 dipswitches according to the desired operation 2 close the rear cover on the key and plug the key into...

Страница 16: ...s of the parameters The remote display IREVXGD000 PST00VR100 shows the temperature with resolution to the tenths between 9 9 C and19 9 C Note the standard display on the user terminal and the remote d...

Страница 17: ...he continuous cycle AUX DOWN SET DEF if pressed together for more than 1 second displays a submenu used to access the HACCP alarm parameters SET DEF If pressed for more than 1 s displays and or lets t...

Страница 18: ...the set point differential temperature monitoring interval interval between defrosts end defrost temperature dripping time alarm thresholds alarm bypass times etc See the parameter table Procedure 1 p...

Страница 19: ...P DOWN button for at least 5 seconds all the changes made to the parameters temporarily stored in the RAM can be cancelled by not pressing any button for 60 seconds thus returning to the standard disp...

Страница 20: ...st deactivation on ir33 On Off To switch the controller off from the keypad press On Off for 3 seconds The display shows the text Off flashing for 3 seconds and then on steady Finally the text Off alt...

Страница 21: ...inally press Prg for 5 seconds to save the value of the parameter HACCP menu The controller must be fitted with the RTC real time clock To enter the HACCP menu press the combination button shown the t...

Страница 22: ...ple in the case of bottle coolers typically used in supermarkets where the doors are opened frequently due to the greater thermal inertia of the liquids compared to the air and the fact that the probe...

Страница 23: ...ogramming key Procedure power down the controller power up while holding Prg mute the display will show the first set bn0 press UP DOWN to select set bn1 to bn6 For example select bn2 press Set to con...

Страница 24: ...reasing order with that configuration Par Description Def Min Max UOM A2 Probe 2 configuration S2 M models 0 0 4 A2 Probe 2 configuration S2 0 Absent 1 Product display only 2 Defrost 3 Condenser 4 Fro...

Страница 25: ...delayed external alarm is thus signal only 3 Probe shown on the display IR33M models On thermometer only models this setting selection is used to exploit the digital input in order to show on the disp...

Страница 26: ...close the door If after being closed for the first time the door remains closed for longer than time d8 or d8d the controller resumes normal operation compressor and evaporator fan switched on if nee...

Страница 27: ...r3 direct reverse operating mode When the contact is open the controller operates in direct mode cooling when the contact is closed in reverse mode heating A switch can therefore be connected to sele...

Страница 28: ...when the internal timer is set Relay output protectors parameters c7 c8 c9 Par Description Def Min Max UOM c0 Compressor fan and AUX start delay at power on 0 0 15 min c1 Minimum time between success...

Страница 29: ...r4 Automatic night time set point variation 3 0 20 20 C F 4 Virtual probe composition 0 control probe S1 100 probe S2 0 0 100 Tab 6 b Parameter 4 is used to determine the virtual probe Sv as the weigh...

Страница 30: ...wn whenever closing pump down valve following low pressure switch activation with no cooling demand c10 Pump down by time or pressure 0 1 pressure time 0 0 1 Tab 6 d Note c8 is a masked parameter and...

Страница 31: ...alarm signal can be ignored by suitably setting parameter c6 alarm bypass after continuous cycle Par Description Def Min Max UOM cc Continuous cycle duration 0 0 15 hour c6 Low temperature alarm bypa...

Страница 32: ...me 4 heater by time with temperature control The defrost can end by temperature in which case the defrost probe Sd must be installed or by time In the first case the defrost ends when the defrost prob...

Страница 33: ...valve Pump down Pump down stage FAN Evaporator fan Def Defrost V_def Hot gas valve Drip Dripping E Evaporator Post drip Post dripping C Condenser S2 Defrost probe V2 Thermostatic expansion valve L Li...

Страница 34: ...situation of this type it is preferable to enable defrost on start up above all if the defrost is controlled by temperature probe on the evaporator therefore avoiding unnecessary defrosts or at least...

Страница 35: ...20 C F Tab 6 o ON OFF FAN F4 F5 Sc F4 F4 0 2 First switch on t t Fig 6 t Key Sc Condenser probe Sv Virtual probe FAN Condenser fans t Time F4 Deactivation temperature F5 Differential Note if no conde...

Страница 36: ...irtual probe 5 Probe 4 2 Probe 1 6 Reserved 4 Probe 3 MSYFCH 0 0 6 I 19 119 R W C P Type of probe 0 NTC Standard Range 50T90 C 1 NTC Enhanced Range 40T150 C 2 PTC Standard Range 50T150 C MSYFCH 0 0 2...

Страница 37: ...shown 4 heater by time with temperature control Ed1 Ed2 not shown SYFCH 0 0 4 I 37 137 R W F dI Maximum time between consecutive defrosts 0 defrost not performed SYFCH 8 0 250 hr min I 38 138 R W F dt...

Страница 38: ...ed SYFCH 0 0 250 min I 54 154 R W C A8 Enable alarms Ed1 and Ed2 end defrost by timeout 0 alarms disabled SYFCH 0 0 1 D 49 49 R W C Ado Light management with door switch Ado Light when ope ning the do...

Страница 39: ...sweat heater function disabled F MSYFCH 0 50 200 C F A 37 37 R W C HrL Remote light relay status on Master 0 disabled MSYFCH 0 0 1 D 62 62 R W C HrA Remote AUX relay status on Master 0 disabled MSYFCH...

Страница 40: ...of parameter sets available I 137 237 R Digital input 1 status D 6 6 R Digital input 2 status D 7 7 R Virtual probe fault alarm D 9 9 R Probe alarm 1 D 10 10 R Probe alarm 2 D 11 11 R Probe alarm 3 D...

Страница 41: ...controller itself on the probes or in network communication An alarm can also be activated from an external contact immediate or delayed See paragraph 5 2 The display shows IA or dA and at the same t...

Страница 42: ...year month day hours minutes and duration in minutes of the selected alarm press Prg mute again to return to the previous list In addition the HACCP alarm menu allows the following operations delete t...

Страница 43: ...nal contact ON ON automatic duty setting A6 duty setting A6 OFF OFF OFF duty setting A6 dA Delayed alarm from external contact ON ON automatic duty setting A6 OFF if A7 0 OFF if A7 0 OFF if A7 0 duty...

Страница 44: ...old or the contact closes the alarm is not signalled and the count is reset When a new alarm condition occurs the count starts from 0 again Parameter A6 has a similar meaning to parameter c4 duty sett...

Страница 45: ...erature alarm threshold Acd Alarm delay cht High cond temperature pre alarm Sc Condenser probe CHT High condensing temperature alarm AE High condensing temperature alarm differential 8 8 Frost protect...

Страница 46: ...1 FLA 6 LRA C300 30000 IRxxxx E A N R C B A M L T xxx R1 R2 8 4 A N O 6 4 A N C 100000 8 A res 2 FLA 30000 IRxxxx 0 L H N R C B A M L T xxx R2 R3 R4 2 2 A N O N C 12 LRA C300 IRxxxx E A P Q S U V X Y...

Страница 47: ...ing cycles 250 V operating cycles PBEVxx E A P S V Y xxx 5A 5 1 A 100000 5A res 1FLA 6 LRA C300 30000 PBEVxx E A N C A L xxx PBEVxx O H N C A L xxx 8 A 8 4 A N O 6 4 A N C 2 2 A N O N C 100000 8 A res...

Страница 48: ...5A on model IRYS0EP 8 A Programming keypad key Special functions HACCP Real Time Clock Function can be enabled when Real Time Clock option available models IR C B L T S U Y Z and on IR33 power models...

Страница 49: ...twork interface Note standard Tab 9 e 9 6 easy wide part numbers Features PBEVS0EAAA PBEVY0EVD0 PBEVC0HND0 PBEVC0HNBA PBEVC0HCAA PBEVH0HNAA PBEVH0HNB0 PBEVH0HNBW PBEVS0SAFA PBEVC0SNFA PBEVC0SNFW Power...

Страница 50: ...PZKEYA0 connected to the computer via the converter IROPZPRG00 When opening the VPM program choose the device to be configured ir33 The Home page is displayed with the options to create a new project...

Страница 51: ...he right button choose Add set for each additional set Fig 10 i Set1 is displayed Fig 10 j Note onthecontroller Set0 Set1 Set6arenamedbn0tobn6respectively Set0 is the default set on the controller i e...

Страница 52: ...d starting from the eighth defrost Note if there are two evaporators the defrost duration used to determine the defrosts to be skipped is the longer nominal defrost duration Possible operating sequenc...

Страница 53: ...2 The following situations may occur if the outputs are not configured or there are probe alarms DEFROST BY TEMPERATURE Defrost probe evap output config Situation Effect Probe 2 defrost output 1 No pr...

Страница 54: ...of operation ON OFF REQ2 CP1 CP2 REQ1 ON OFF ON OFF OFF ON EXAMPLE 1 t t t t Fig 11 d ON OFF REQ2 CP1 CP2 REQ1 ON OFF ON OFF OFF ON EXAMPLE 2 t t t t Fig 11 e ON OFF REQ2 CP1 CP2 REQ1 ON OFF ON OFF OF...

Страница 55: ......

Страница 56: ...EL INDUSTRIES Headquarters Via dell Industria 11 35020 Brugine Padova Italy Tel 39 049 9716611 Fax 39 049 9716600 e mail carel carel com www carel com Agenzia Agency ir33plus 0300028EN rel 1 1 05 05 2...

Отзывы: