28
ENG
ir0300028EN rel. 1.1 - 05.05.2017
12 = Auxiliary output
Set H1 and/or H5 = 2 to activate the auxiliary output.
See the table at the start of this paragraph for details on the activation/
deactivation logic.
13 = Door switch with compressor and fan off , light not managed
Operation is similar to A4=5, with the diff erence that the light output is
not modifi ed.
Note:
the light management algorithm depends on parameter Ado
– “Light management with door switch” (masked parameter accessible
from VPM).
Ado Light when ope-
ning the door
Algorithm Description
0
off normal
open-close
on
extended open-close-open-close
1
off extended open-close-open-close
on
normal
open-close
Tab. 5.j
If the digital input is selected to not manage the light (A4, A5, A9 =13 or
14), the algorithm is modifi ed as follows:
Ado Light when ope-
ning the door
Algorithm Description
0
off normal
open-close
on
extended open-close-open-close
1
off normal
open-close
on
normal
open-close
Tab. 5.k
See the table at the start of this paragraph for details on the activation/
deactivation logic.
14 = Door switch with fan off only, light not managed
Operation is similar to A4=9, with the diff erence that the light output is
not modifi ed.
Note:
the light management algorithm depends on parameter Ado,
as shown in the previous table.
See the table at the start of this paragraph for details on the activation/
deactivation logic.
5.3 Digital
outputs
The parameters in question concern the minimum on or off times of the
same output or diff erent outputs, so as to protect the loads and avoid
swings in control.
Important:
for the times set to become immediately operational,
the controller needs to be switched off and on again. Otherwise, the
timers will become operational when the controller is next used, when
the internal timer is set.
R
elay output protectors (parameters c7,c8,c9)
Par. Description
Def
Min Max UOM
c0
Compressor, fan and AUX start delay at power
on
0
0
15
min
c1
Minimum time between successive compres-
sor starts
0
0
15
min
c2
Minimum compressor off time
0
0
15
min
c3
Minimum compressor on time
0
0
15
min
Tab. 5.l
•
c0: when the controller is powered on, the compressor, evaporator
fans and auxiliary relay in neutral zone control (‘H1’=11 or ‘H5’=11)
are started after a delay (in minutes) equal to the value assigned to
this parameter. The delay is used to protect the compressor against
repeated starts in the event of frequent power failures;
•
c1 defi nes the minimum time between two consecutive starts of the
compressor;
•
c2 defi nes the minimum compressor off time;
•
c3 defi nes the minimum compressor on time;
O
ther relay output protectors (parameter c11)
Par.
Description
Def
Min Max UOM
c11
Second compressor start delay
4
0
250
s
Tab. 5.m
•
c11 defi nes the activation delay between the fi rst and second
compressor (or between the fi rst and the second compressor step).
c1
ON
OFF
ON
OFF
t
STEP1
STEP2
c3
c2
c11
c0
POWER_ON
Fig. 5.h
Key
Step1
Compressor step 1
Step2
Compressor step 2
t
time
F
unctions assigned to AU
X
1/AU
X
2
Outputs AUX1 and AUX2 can be assigned diff erent functions, such as
alarm signal, auxiliary output, light output, pump down valve, condenser
fan, reverse output with neutral zone, second compressor, second
compressor with rotation. For details, see the chapter on control.
Par.
Description
Def
Min Max UOM
H1
AUX1 output confi guration
1
0
13
-
0 = normally energised alarm
1 = normally de-energised alarm
2 = auxiliary
3 = light
4 = auxiliary evaporator defrost
5 = pump down valve
6 = condenser fan
7 = delayed compressor
8 = auxiliary with deactivation when OFF
9 = light with deactivation when OFF
10 = no function
11 = reverse with neutral zone
12 = second compressor step
13 = second compressor step with rotation
H5
AUX2 output confi guration
See H1
3
0
13
-
Tab. 5.n