CDE500 Vector Control AC Drive
Chapter 6 Parameters Description
1: Stop according to the stop mode
2: Continue to run at 8% of rated motor frequency and resume to the set
frequency if the load recovers
Ten's digit: Motor overheat
Same as unit's digit in
F0.19
Hundred's digit: External Fault
Same as unit's digit in
F0.19
Thousand's digit: RS485 communication fault
Same as unit's digit in
F0.19
F0.21
Range: 0000~2222
Default: 0000
Fault protection
action selection 3
Unit's digit: Optional card communication fault
Same as unit's digit in
F0.19
Ten's digit: PID feedback over range
Same as unit's digit in
F0.19
Hundred's digit: Accumulative power-on time reached
Same as unit's digit in
F0.19
Thousand's digit: Accumulative running time reached
Same as unit's digit in
F0.19
F0.22
Range: 0000~2222
Default: 0000
Fault protection
action selection 4
Unit's digit: Too large speed deviation
Same as unit's digit in
F0.19
Ten's digit: Motor over speed
Same as unit's digit in
F0.19
Hundred's digit: Flux pole detection fault
Same as unit's digit in
F0.19
Thousand's digit: UVW signal feedback fault
Same as unit's digit in
F0.19
F0.23
Range: 0000~2222
Default: 0000
Fault protection
action selection 5
Unit's digit: Encoder fault
0: Coast to stop
1: Switch over to V/F control, stop according to the stop mode
2: Switch over to V/F control, continue running
Ten's digit: User-defined fault 1
Same as unit's digit in
F0.19
Hundred's digit: User-defined fault 2
Same as unit's digit in
F0.19
Thousand's digit: Interlock warning during multi-pump operation
mode
Same as unit's digit in
F0.19
Содержание CDE500 Series
Страница 8: ......
Страница 28: ...CDE500 Vector Control AC Drive Chapter 2 Product Information 15 C01 C02 A B D H1 W H C03 ...
Страница 282: ......