CDE500 Vector Control AC Drive
Chapter 6 Parameters Description
E5.31
Range: 0.00~
b0.00
Default: 5.00
Minimum
frequency of PID
feedback
detection
Unit: Hz
When the PID output frequency is smaller than
E5.31
,the AC drive will not
detect whether PID feedback is lost even if
E5.30
=1.
E5.32
Range: 0.0~600.0
Default: 0.0
Waiting time of
PID feedback
detection
Unit: Sec
When
E5.30
=1 and the PID output frequency is higher than
E5.31
for the
time
E5.32
set,the AC drive will detect whether PID feedback is lost .
E5.33
Range:
E5.03
~
E5.02
Default: 100.0
Upper limit of PID
feedback
detection
Unit: %. Unit/Decimal depends on
E5.00
/
E5.01
.
The AC drive will not report any error when the PID feedback is between
E5.34
~
E5.33
.Otherwise,when the lasting time exceeds E5.35, Er35 “PID
feedback over range” will be reported.
E5.34
Range:
E5.03
~
E5.02
Default: 0.0
Lower limit of PID
feedback
detection
Unit: %.Unit/Decimal depends on
E5.00
/
E5.01
.
See the description of
E5.33
.
E5.35
Range: 0.0~600.0
Default: 0.0
Detection time of
PID feedback
detection
Unit: Sec
See the description of
E5.33
.
These parameters are used to judge whether PID feedback is lost..
Figure 6- 39 PID feedback detection function