CDE500 Vector Control AC Drive
Chapter 6 Parameters Description
Table 6- 10 Switch input and output function table
Setting
Function
Description
0
No output
The output terminal is invalid, and not output signal.
1
Under voltage
When the bus voltage is below the under voltage level, the terminal
output “ON” signal, and LED display “Er07”.
2
Ready for run
The AC drive is waiting for operation or has been running and without
any fault, the terminal output “ON” signal.
3
Running
The AC drive output “ON” signal when running and output “OFF”
signal when stop.
4
Zero-speed running 1
(no output at stop)
The AC drive is in the running state and the output frequency is 0HZ,
the output signal is “ON”.
5
Zero-speed running 2
(having output at stop)
As long as the AC drive output frequency is 0HZ, no matter whether
the AC drive running or stop, the terminal stall output “ON” signal.
6
Reverse running
When the AC drive in running reverse mode, the terminal output
“ON” signal.
7
Frequency reached
When the D-value of output frequency and set frequency is less than
Eb.08(Frequency reaches the detection width), the terminal output
“ON” signal.
8
Frequency upper limit
reached
When the AC drive output frequency reaches the upper limit
frequency, the terminal output ON signal.
9
Frequency lower limit
Reached (no output at
stop)
When the output frequency decelerate to the lower limit frequency,
the terminal output ON signal.
The terminal still output OFF signal when stop.
10
FDT1 detection output
Reference to Eb.13(FDT1 detection value) and Eb.14(FDT1
detection lag value) parameters description.
11
FDT2 detection output
Reference to Eb.15(FDT5 detection value) and Eb.16(FDT2
detection lag value) parameters description.
12
Torque limited
In the speed control mode, if the output torque reaches to the torque
limit value, then the terminal output ON signal.
13
Fault output(VFD stop)
When the AC drive shutdown due to a fault, the terminal output ON
signal.
14
Warning output
(continue running)
The AC drive has warning and continue running, then the terminal
output ON signal.
15
Motor overload
pre-warning
When the output current exceeds the cumulative of overload inverse
time curve and F0.08(Motor overload warning coefficient), the
terminal output ON signal. See details about F0.08.
16
VFD overload
prewarning
The terminal output ON signal when the AC drive into the overload
inverse time calculation.