Group E4: Acc & Dec time
The AC drive provides a total of four groups of acceleration/deceleration time, that is the
following three groups and the group defined by
b0.04
and
b0.05
. Definitions of four groups are
completely the same,see the descriptions of
b0.04
and
b0.05
.You can switch over between the four
groups of acceleration/deceleration time through different state combinations of X terminals. For
more details, see the function No.20 and No.21 descriptions of
C0.01
.
The descriptions of
E4.00
~
E4.05
are the same with
b0.04
~
b0.05
,ranges from 0.1 to 6000.0
seconds,defaults to model dependent.
E4.00
Acceleration time 2
E4.02
Acceleration time 3
E4.04
Acceleration time 4
E4.01
Deceleration time 2
E4.03
Deceleration time 3
E4.05
Deceleration time 4
E4.06
Range: 0.00~
b0.00
Default: 0.00
Frequency switchover point
between acceleration time 1&2
Unit: Hz
See the following figure.
E4.07
Range: 0.00~
b0.00
Default: 0.00
Frequency switchover point
between deceleration time 1&2
Unit: Hz
See the following figure.
The AC drive can switchover automatically between Acceleration/Deceleration time 1 and 2
with no X terminal signal when setting proper
E4.06
or
E4.07
.In acceleration process,the time 2 will
be used when output frequency is lower than
E4.06
,otherwise time 1 will be used.In deceleration
process,the time 1 will be used when output frequency is higher than
E4.07
,otherwise time 2 will be
used.
If any X terminal is set as
20~21 function
(Acceleration/Deceleration
time select),the actual
acceleration/deceleration
time will be determined by X
terminal states.
Figure 6- 34 Acceleration/Deceleration time 1/2 switching
E4.08
①
Range: 0~2
Default: 1
Unit of Acceleration/
Deceleration time
0: 1s (second)
1: 0.1s
2: 0.01s
Available for acceleration/deceleration time 1 to 4.
E4.09
①
Range: 0~2
Default: 1
Reference frequency
of Acceleration/
Deceleration time
0: Max frequency(b0.00)
1: Current setting frequency
2: 100Hz
Acc/Dec time is defined as the running time needed between 0Hz to
E4.09