Chapter 6 Parameters Description
C2.07
Range: -100.0~100.0
Default: 100.0
Corresponding
setting of AI
curve 1 maximal
input
Unit: %
The relationship between AI curve 1 maximal input signal and the
percentage of set value.
C2.08
Range: -10.00~C2.10
Default: 0.00
AI curve 2
minimum input
Unit: V
AI curve 2 minimum input signal
C2.09
Range: -100.0~100.0
Default: 0.0
Corresponding
setting of AI
curve 2 minimum
input
Unit: %
The relationship between AI curve 2 minimum input signal and the
percentage of set value.
C2.10
Range: C2.08~10.00
Default: 10.00
AI curve 2
maximal input
Unit: V
AI curve 2 maximal input signal
C2.11
Range: -100.0~100.0
Default: 100.0
Corresponding
setting of AI
curve 2 maximal
input
Unit: %
The relationship between AI curve 2 maximal input signal and the
percentage of set value.
Both curve 1 and curve 2 are two point curves.
AI1,AI2 can select -10~10V voltage input or 0~20mA current input through jumper terminal
CJ1 and CJ2 on the control board.
When chose the 0~20mA current input, 0mA corresponding to the 0V, and 20mA
corresponding to 10V.
Example:
The maximum frequency of b0.00 = 50.00 HZ
The frequency selection method of b2.05 = 00
(Chose main frequency source A as output)
The Main frequency source A selection b2.00 = 1
(Main frequency source A select AI1)
The analog input AI curve selection C2.03 = 321(AI1 choice AI curve 1)
The minimal input of AI curve 1 C2.04 = 0.00V
The corresponding setting of AI curve 1 minimal input C2.05 = 0.0%
The maximal input of AI curve 1 C2.06 = 10.00V
The corresponding setting of AI curve 1 maximal input C2.07 = 100.0%
When AI1 = 4V, the output frequency of this time is: 50.00*
(
4.00/10.00
)
= 20.00Hz