CDE500 Vector Control AC Drive
Chapter 6 Parameters Description
-119-
b2.06
Range: 000~999
Default: 000
Binding
command source
to frequency
source
It is used to bind the three running command sources with the nine
frequency sources, facilitating to implement synchronous switchover.
Unit's digit: Binding the frequency source together with Keypad
control source
0: No binding
1: Frequency source by digital setting
b2.01
+UP/DOWN
2: AI1
3: AI2
4: AI3
5: Pulse setting (DI5)
6: Multi-reference
7: Simple PLC
8: PID
9: Communication setting
Ten's digit: Binding the frequency source together with Terminal
control source
0–9, same as unit's digit
Hundred's digit: Binding the frequency source together with
Communication control source
0–9, same as unit's digit
Note:
Different running command sources can be bound to the same
frequency source.
if a command source has a bound frequency source, the frequency
source set in b2.00 to b2.05 no longer takes effect when the command
source is effective.
b2.07
①
Range: 1~2
Default: 2
Frequency
resolution
It is used to set the resolution of all frequency-related parameters.
1: Minimum unit is 0.1 Hz
2: Minimum unit is 0.01 Hz
If the resolution is 0.1 Hz, the AC drive can output up to 3000.0
Hz(CDE500B type). If the resolution is 0.01 Hz, the AC drive can output
up to 600.00 Hz.
Note:
Modifying this parameter will make the decimal places of all
frequency-related parameters change and corresponding frequency
values change(pay attention to the rated motor frequency specially, b0.09
will change from 50.00Hz to 500.0Hz when set b2.07 from 1 to 2).Please
confirm again after the operation of motor, otherwise it may cause
personal and property losses.