Figure 6- 46 Schematic diagram of removing pump logic
E6.12
Range: 0.00~
b0.00
Default: 48.00
Add pump
frequency 2
Unit: Hz
The frequency to add the second auxiliary pump(controlled via a Y/T
terminal with No.42 function “Motor 3# Control output”).
The second auxiliary pump startup conditions:
Only one auxiliary pump is running.
AC drive output frequency is higher than E6.12+1Hz,and the lasting
time exceeds
E6.16
.
E6.13
Range: 0.00~
E6.12
Default: 25.00
Reduce pump
frequency 2
Unit: Hz
The frequency to remove the second auxiliary pump(controlled via a Y/T
terminal with No.42 function “Motor 3# Control output”).
The second auxiliary pump stop conditions:
Two auxiliary pump are running.
AC drive output frequency is lower than E6.13-1Hz,and the lasting
time exceeds
E6.17
.
E6.14
Range: 0.00~
b0.00
Default: 48.00
Add pump
frequency 3
Unit: Hz
The frequency to add the third auxiliary pump(controlled via a Y/T terminal
with No.43 function “Motor 4# Control output”).
The third auxiliary pump startup conditions:
Two auxiliary pump are running.
AC drive output frequency is higher than E6.14+1Hz,and the lasting
time exceeds
E6.16
.