6. Normal operation
6. Normal operation
Figure 6.34 Fixed-PF
版本号
2015-02-23 19 35
Fixed-PF
2015-02-23 19 35
Power Factor
:
+1.00
E S C
U P
D O W N
E N T
Y E S
=
< E N T >
N O
=
< E S C >
4.Fixed-PF
Description: Inverter will output power with fixed power factor.
Setting Range: -0.8 to +0.8
Default value is PF = 1
5. Reac-power (Not Required)
Description: Inverter will generate reactive power based on changing output power.
Note: This Setting is NOT required by Rule21 Standards.
This function is for maintenance personnel only, wrong operation
will prevent the inverter from reaching maximum power.
6. P-factor (Not Required)
Description: Inverter will change power factor based on changing output power.
Note: This Setting is NOT required by Rule21 Standards.
This function is for maintenance personnel only, wrong operation
will prevent the inverter from reaching maximum power.
7.VgWatt-UL (Not Required)
Description: Inverter will change the active output power based on voltage change.
Note: This Setting is NOT required by Rule21 Standards.
This function is for maintenance personnel only, wrong operation
will prevent the inverter from reaching maximum power.
8. Enable both Volt-Var and Volt-Watt modes
Description: Rule21 requires both Volt-var and Volt-watt modes can be enabled.
To set both modes (Volt-var in high priority)
Step 1: Select and set Volt-watt mode at first.
Step 2: Enter "Working Mode" again and select and set Volt-var mode then.
Step 3: To check the priority, a new mode will appear as "V-Q & V-P" which
indicates (Q) Volt-var is in high priority.
Figure 6.22 Working Mode set(1)
Working Mode Set
2015-02-23 19 35
Work Mode:
E S C
U P
D O W N
E N T
Y E S
=
< E N T >
N O
=
< E S C >
V-Q&V-P
To set both modes (Volt-watt in high priority)
Step 1: Select and set Volt-var mode at first.
Step 2: Enter "Working Mode" again and select and set Volt-watt mode then.
Step 3: To check the priority, a new mode will appear as "V-P & V-Q" which
indicates (P) Volt-watt is in high priority.