6. Normal operation
6. Normal operation
The screen shows the inverter total energy (lifetime) detail (see Figure 6.20).
6.6.8 Total Energy
Figure 6.20 Total generating capacity details
2015-02-23 19 35
0 . 0
0 . 5
1 . 0
1 . 5
2 . 0
2 . 5
3 . 0
T
o
ta
l E
n
e
r
g
y
[M
W
h
]
2 0 0 6
2 0 0 7
2 0 0 8
2 0 0 9
2 0 1 0
2 0 11
2 0 1 2
2 0 1 3
2 0 1 4
2 0 1 5
0 0 . 0 1
Total Energy
Select Advanced Settings from the main menu (see Figure 6.21) to access the following
options. Enter password as described in Section 6.6.
6.7 Sub-menu “Advanced Settings” – Technicians only
Figure 6.21 Advanced settings
6.7.1 Select Standard
Select grid standard (see Figure 6.22).
NOTE
This function is for authorized technicians only. Improper access and
operation may result in abnormal results and damage to the inverter.
Password required – restricted access – authorized technicians only.
Unauthorized access will void the warranty.
Advanced
Set
.
2015-02-23 19 35
Grid
ON
/
OFF
Power Control
Clear
Energy
Restore
Settings
Restart
HMI
NOTE
This is for service technicians only. The inverter is customized according to
the local standard before shipping. There should be no requirement to set
the standard.
The "User-Def" function can be only used by the service engineer, and
changing the protection level must be approved by the local grid company.
Calibrate
Reset
Password
Special Settings
STD.Mode Settings
External EPM set
Select
Standard
Figure 6.22 Select grid standard
Select Standard
2015-02-23 19 35
Select
Standard
E S C
U P
D O W N
E N T
Y E S
=
< E N T >
N O
=
< E S C >
R21P3-480
Press the UP or DOWN key to select the standard (AS4777, VDE4105, R21P3-480, G59/3,
CQC, User-Def function, etc.). Press the ENTER key to confirm the setting. Press the ESC
key to cancel changes and return to the previous menu.
Rule 21 uses the standard R21P3-480 for applications not requiring arc fault and
R21P3-48A for applications requiring arc fault
protection.
Standard UL-480V/UL-480V-A/ISONE480A are used where Rule 21 is not required.
Selecting the User-Def sub menu will access to the following sub menu (see Figure 6.23).
The User-Def screen shows the parameters that can be adjusted for local grid conditions
(see Figure 6.23). This section is for service technicians only.