6. Normal operation
6. Normal operation
.67.
.66.
5. Reac-power (Not Required)
Description: Inverter will generate reactive power based on changing output power.
Note: This Setting is NOT required by UL1741SA Standards.
This function is for maintenance personnel only, wrong operation
will prevent the inverter from reaching maximum power.
6. P-factor (Not Required)
Description: Inverter will change power factor based on changing output power.
Note: This Setting is NOT required by UL1741SA Standards.
This function is for maintenance personnel only, wrong operation
will prevent the inverter from reaching maximum power.
7.VgWatt-UL
Description: Inverter will change the active output power based on voltage change.
Note: This is the Volt-Watt Setting for UL1741SA Standards.
Default Settings for UL1741SA:
Rated 480V Grid
V1:less than V2
V2:less than Vstart
V3 (Vstart): (277-333V) Default305V
V4 (Vstop): (305-360V) Default 333V
P1:100% P2:100% P3: 100% P4:0%
100
%
of
Input
Power
Vmin
Vnom
Vstart
Vstop
Vmax
AC Volt
0
Figure 6.28 Volt
-
Watt
characteristic
Figure 6.34 VgWatt-UL
版本号
2015-02-23 19 35
VgWatt-UL
2015-02-23 19 35
Voltage1 :
Voltage2 :
P-Limit1 :
P-Limit2 :
242V
273V
100%
100%
S E T
=
< E N T >
D O N E
=
< E S C >
Voltage3 :
P-Limit3 :
305V
100%
Voltage4 :
P-Limit4 :
333V
000%
Canadian Solar US version inverters have Ten working modes:
1. Null
2. Volt-watt
3. Volt-Var
4. Fixed-PF
5. Reac-power
6. P-factor
7. VgWatt-UL
6.7.9.1.2 With Rule21 Standard selected
NOTE
The other three working mode"P1-V-Watt","P1-V-Var" and
"P1-V-P&V-Q" are NOT applicable for settings.
Based on Rule21, working mode 1,2,3,4 can be used by grid operator.
NOTE
The following modes are for "R21P3-480", "R21P3-48A".