11
Programming
Menu:
From any operation status, pressing the knob for 5 seconds, displays
the "Programming Menu".
Access to the menu requires the Password.
Installer
Menu:
Confirm with the knob to enter the
menu.
Exit from "Programming Menu"
Installer Menu:
Password entry for menu access.
Setting the identification number of
the appliance for connection to the
BUS.
Enable T1 or T2 probe for
disinfection.
Maximum temperature limit setting
for system protection.
Thermal shock temperature setting.
Setting the minimum time during
which the temperature must remain
above the set temperature for the
thermal shock.
Setting the maximum time available
within which it is possible to
perform the thermal shock.
RESET. Control to reset the device
to factory default conditions. ON/
OFF selection, activating the ON
option, the device resets the
default parameters and initializes
the device.
Temperature measurement unit
selection.
Flow temperature setting at the
adjustment phase.
Day setting.
Month setting.
Year setting.
Time format setting to 12H or 24H.
Time setting.
Default T2
Default 65°C
Default 65°C
Default 5 min.
Default 24H
Default 48°C
Default °C
Default OFF
Default: 2222
Default: 1
Default: 10 min
Default 1
Default 1
Default 17
Default 00:00