ALARM CODE

ALARM REPRESENTATION

ALARM DESCRIPTION

ALARM TYPE

RELAY STATUS / WORK STATUS

RECORDING

POSSIBLE CAUSE

REMEDY

AL01

file originale

1
2
3
4
5

6

7
8
9

10

11

12

13

MOTOR OR ADJUSTMENT SCREW LOCKING: 

possible locking of the adjustment screw 

in an intermediate position

BLOCKING ALARM  

OUT1 NC = Closed

OUT2 = Open

OUT3 = Open

The device remains blocked and sets in its 

closing position, performs the zero and full 

scale acquisition after the “Reset Alarms” 

control

YES

- OPERATING SCREW MECHANICAL BLOCK

- MOTOR PHASE SHIFT

- REGULATOR-ACTUATOR FIXING SCREWS 

LOOSENING

- "Reset alarms" control: The device 

performs the zero and full scale acquisition 

to check that the stroke set is congruent, if it 

does not find mechanical blocks it resumes 

normal operation; if during the "Alarms reset" 

control it does not find the correct stroke, 

check manually if it performs a 1.5 turn 

rotation 

- Check the screws tightening

AL02

file originale

1
2
3
4
5

6

7
8
9

10

11

12

13

MAINS VOLTAGE BLACKOUT: 

indicates that there was an electric supply 

failure for

 less than 60 minutes

NON-BLOCKING ALARM: 

When the electric supply is 

restored it resumes normal 

operation

OUT1 NC = Closed

OUT2 = Closed if set

OUT3 = Open

When the electric supply is resumed, the 

device restarts the water mixing

YES, at the 

return

 of the electric 

supply mains

- MAINS BLACKOUT

- BOARDS CONNECTOR NOT FIXED 

CORRECTLY

- Check mains electric supply 

The alarm is not recorded in the alarm log; 

after 5 minutes the alarm is

automatically deleted

AL03

file originale

1
2
3
4
5

6

7
8
9

10

11

12

13

DISINFECTION FAILED: 

indicates a failed disinfection

NON-BLOCKING ALARM

OUT1 NC = Closed

OUT2 = Closed if set

OUT3 = Open

The device returns to the water mixing 

status, the first successful disinfection 

clears the alarm condition but records it in 

the log of the last failed disinfections; the 

display shows the symbol "Manual".

YES, it is also

recorded in the

last 10

disinfection 

failed

- DISINFECTION NOT PERFORMED 

ACCORDING TO THE PARAMETERS SET

- The alarm condition is cleared at the next 

successful disinfection or by means of the 

"Reset alarms" control. The result of the 

disinfection is kept in the log of the last 

10 failed disinfections. If the error occurs 

frequently, check that the parameters set are 

congruent with the system

- Check the recirculation circuit

- Check inlet IN2 contact closing

AL04

file originale

1
2
3
4
5

6

7
8
9

10

11

12

13

THERMAL SHOCK FAILED: 

indicates a failed thermal shock

NON-BLOCKING ALARM

OUT1 NC = Closed

OUT2 = Closed if set

OUT3 = Open

The device returns to the water mixing 

status

YES

- THERMAL SHOCK NOT PERFORMED 

ACCORDING TO THE PARAMETERS SET

- The alarm condition is cleared at the next 

successful thermal shock or through the 

"Reset alarms” control

- Check the parameters

- Check the recirculation circuit

- Check inlet IN2 contact closing

AL05

file originale

1
2
3
4
5

6

7
8
9

10

11

12

13

DEVICE MAXIMUM TEMPERATURE 

EXCEEDING (90°C): 

indicates that the flow probe T1 has read a 

temperature value greater than 90°C

SELF-RESETTING BLOCKING 

ALARM: 

The device resumes its operation 

when the probe T1 returns to the 

set value

OUT1 NC = Closed

OUT2 = Open

OUT3 = Open

The appliance sets to the closing position

YES

- SYSTEM ANOMALY

- FAULTY FLOW PROBE

- Check the operation of the system or check 

the actual value measured by the probe 

comparing it with suitable instruments

15

14

- LOOSE MOTOR CONNECTORS

- Check the motor connectors

Содержание LEGIOMIX 6000 series

Страница 1: ...and default values Display menu Programming Menu Installer Menu Alarm management General diaphragm 2 3 6 8 7 10 11 14 PROGRAMMING MANUAL Copyright 2018 Caleffi H0004567 01 www caleffi com Disinfection...

Страница 2: ...ved It is recommended to refer to the alarm section in this manual For correct battery installation see the Installation and commissioning manual supplied in the package When the battery checks are co...

Страница 3: ...evice does not perform the disinfection Operating status During the operation of the device the following work states can be displayed 1 Reached setpoint 2 Adjustment in progress 3 Disinfection in pro...

Страница 4: ...rts are in orange b Disinfection in progress with control on return probe T2 see table on page 5 In this mode the device performs thermal disinfection which consists in raising the mixed water tempera...

Страница 5: ...be T1 d2 Disinfection performed at the minimum disinfection temperature diS C Disinfection check performed on probe T1 Disinfection type with recirculation probe T2 enabled Disinfection Code Descripti...

Страница 6: ...set tHi diS or with the manual opening of the contact Manual activation through button Automatic end The disinfection status ends as soon as the minimum disinfection time tmin diS is exceeded or withi...

Страница 7: ...Reset alarms control Additionally the zero acquisition mode is activated whenever an electric supply failure occurs for at least 60 minutes and at the outlet from any disinfection thermal shock It is...

Страница 8: ...om 00 to 99 17 14 Time format selection 12H 24H 24H 15 Hours minutes setting 0 23 hours 0 59 minutes 00 00 16 Daylight saving time setting YES on NO off On 17 Disinfection program change d1 d2 d2 18 T...

Страница 9: ...hatever status the appliance is in it is always possible to navigate around the various menus to read and change the various settings The general menu structure is as follows Display menu Press the kn...

Страница 10: ...or the day set is displayed the segment below the number indicates its activation Maximum time within which it is possible to perform the disinfection Maximum flow temperature limit it is a system pro...

Страница 11: ...uring which the temperature must remain above the set temperature for the thermal shock Setting the maximum time available within which it is possible to perform the thermal shock RESET Control to res...

Страница 12: ...x time bands that can be set for recirculation OUT2 activation 1 02 00 and 05 59 4 14 00 and 17 59 2 06 00 and 09 59 5 18 00 and 21 59 3 10 00 and 13 59 6 22 00 and 01 59 Installer Menu password chang...

Страница 13: ...of the valve Perform with closed shut off valves The number of times the error has occurred appears in the top right of the screen To delete the alarms from the sub menu use the Reset Alarms Installe...

Страница 14: ...F RESETTING BLOCKING ALARM The device resumes its operation when the probe T1 returns to the set value Alarm management To make it easier to resolve any functional faults that occur after installation...

Страница 15: ...er mixing status the first successful disinfection clears the alarm condition but records it in the log of the last failed disinfections the display shows the symbol Manual YES it is also recorded in...

Страница 16: ...failure for more than 60 minutes NON BLOCKING ALARM When the electric supply is restored it resumes normal operation after performing the zero acquisition AL08 FAULTY FLOW PROBE SELF RESETTING BLOCKIN...

Страница 17: ...NC Closed OUT2 Closed OUT3 Open The device can only perform the water mixing while maintaining the alarm active YES PROBE T2 NOT CONNECTED OR DAMAGED Check that the probe is present and correctly con...

Страница 18: ...18...

Страница 19: ...19...

Страница 20: ...20...

Отзывы: