8

No.

Parameter

Description

Setting range

Factory (default) 

configuration

1

“Installer Menu” access password

0000-9999

2222

2

Identifies the product among those connected 

to the BUS

from 1 to 255

1

3

Disinfection probes enable

T1 = flow probe enabled

T2 = recirculation probe enabled

T2

4

Maximum temperature limit: system protection

from 65°C to 85°C

65°C

5

Thermal shock temperature

from 65°C to 85°C

65°C

6

Minimum time for which the temperature must 

remain above the set temperature for the 

thermal shock

from 1 to 4320 minutes

0005 minutes

7

Maximum time available within which it is 

possible to perform the thermal shock

from 1 to 4320 minutes

0010 minutes

8

Control to reset the device to factory default 

configuration

on – oFF

oFF

9

Temperature measurement unit

C = Celsius

F = Fahrenheit

C

10

Flow temperature in adjustment phase

from 35°C to 65°C

48°C

11

Day setting

from 01 to 31

01

12

Month setting

from 01 to 12

01

13

Year setting

from 00 to 99

17

14

Time format selection

12H - 24H

24H

15

Hours/minutes setting

0 - 23 hours

0 - 59 minutes

00:00

16

Daylight saving time setting

YES = on

NO = off

On

17

Disinfection program change

d1-d2

d2

18

Type of inlet IN1 selection

In1 - In2 - In3

In2

19

ECO mode

on - oFF

oFF

20

Minimum disinfection temperature setting

from 50°C to 85°C

60°C

21

Disinfection start day, time and minutes setting

1 2 3 4 5 6 7

1 2 3 4 5 6 7 at

time 02:00

22

Minimum time for which the temperature 

must remain above the set temperature for 

disinfection

from 0 to 600 minutes

0030 minutes

23

Maximum time available within which it is 

possible to perform the disinfection

from 3 to 900 minutes

0060 minutes

24

OUT2 relay enable in the 6 time bands

1 2 3 4 5 6

1 2 3 4 5 6

25

Valve DN size

15-20-25-32-40-50

Depending on the

valve

26

Communication protocol parity

EVEn - nonE 

EVEn

Operating parameters and default values

The operating parameters can be set in the appropriate menus, and are summarised in the following table:

To ensure proper operation of the device, set the maximum temperature of the system (T1 Hi) 5°C higher than the adjustment temperature 

value (T1).

9  

Содержание LEGIOMIX 6000 series

Страница 1: ...and default values Display menu Programming Menu Installer Menu Alarm management General diaphragm 2 3 6 8 7 10 11 14 PROGRAMMING MANUAL Copyright 2018 Caleffi H0004567 01 www caleffi com Disinfection...

Страница 2: ...ved It is recommended to refer to the alarm section in this manual For correct battery installation see the Installation and commissioning manual supplied in the package When the battery checks are co...

Страница 3: ...evice does not perform the disinfection Operating status During the operation of the device the following work states can be displayed 1 Reached setpoint 2 Adjustment in progress 3 Disinfection in pro...

Страница 4: ...rts are in orange b Disinfection in progress with control on return probe T2 see table on page 5 In this mode the device performs thermal disinfection which consists in raising the mixed water tempera...

Страница 5: ...be T1 d2 Disinfection performed at the minimum disinfection temperature diS C Disinfection check performed on probe T1 Disinfection type with recirculation probe T2 enabled Disinfection Code Descripti...

Страница 6: ...set tHi diS or with the manual opening of the contact Manual activation through button Automatic end The disinfection status ends as soon as the minimum disinfection time tmin diS is exceeded or withi...

Страница 7: ...Reset alarms control Additionally the zero acquisition mode is activated whenever an electric supply failure occurs for at least 60 minutes and at the outlet from any disinfection thermal shock It is...

Страница 8: ...om 00 to 99 17 14 Time format selection 12H 24H 24H 15 Hours minutes setting 0 23 hours 0 59 minutes 00 00 16 Daylight saving time setting YES on NO off On 17 Disinfection program change d1 d2 d2 18 T...

Страница 9: ...hatever status the appliance is in it is always possible to navigate around the various menus to read and change the various settings The general menu structure is as follows Display menu Press the kn...

Страница 10: ...or the day set is displayed the segment below the number indicates its activation Maximum time within which it is possible to perform the disinfection Maximum flow temperature limit it is a system pro...

Страница 11: ...uring which the temperature must remain above the set temperature for the thermal shock Setting the maximum time available within which it is possible to perform the thermal shock RESET Control to res...

Страница 12: ...x time bands that can be set for recirculation OUT2 activation 1 02 00 and 05 59 4 14 00 and 17 59 2 06 00 and 09 59 5 18 00 and 21 59 3 10 00 and 13 59 6 22 00 and 01 59 Installer Menu password chang...

Страница 13: ...of the valve Perform with closed shut off valves The number of times the error has occurred appears in the top right of the screen To delete the alarms from the sub menu use the Reset Alarms Installe...

Страница 14: ...F RESETTING BLOCKING ALARM The device resumes its operation when the probe T1 returns to the set value Alarm management To make it easier to resolve any functional faults that occur after installation...

Страница 15: ...er mixing status the first successful disinfection clears the alarm condition but records it in the log of the last failed disinfections the display shows the symbol Manual YES it is also recorded in...

Страница 16: ...failure for more than 60 minutes NON BLOCKING ALARM When the electric supply is restored it resumes normal operation after performing the zero acquisition AL08 FAULTY FLOW PROBE SELF RESETTING BLOCKIN...

Страница 17: ...NC Closed OUT2 Closed OUT3 Open The device can only perform the water mixing while maintaining the alarm active YES PROBE T2 NOT CONNECTED OR DAMAGED Check that the probe is present and correctly con...

Страница 18: ...18...

Страница 19: ...19...

Страница 20: ...20...

Отзывы: