4.4.7
V1SET
It is the second of the two allowed Voltage programmable values (in absolute value).
It is active when the VSEL input signal is TRUE. It can be programmed either via Local
or Remote Control.
4.4.8
I1SET
It is the second of the two allowed Current Limit programmable values (in absolute
value).
It is active when the ISEL input signal is TRUE. It can be programmed either via Local or
Remote Control.
4.4.9
RAMP-UP
(RUp)
Maximum Voltage programmable increase rate expressed in Volt/second. When a
channel is switched On, or when it is switched from a lower Voltage value to a higher
one, the Voltage output drifts from one value to the other at the rate expressed by the
Ramp-Up parameter.
It can be programmed either via Local or Remote Control.
4.4.10
RAMP-DOWN
(RDwn)
Maximum Voltage programmable decrease rate expressed in Volt/second (in absolute
value). When a channel is switched Off, or when it is switched from a higher Voltage
value to a lower one, the Voltage output drifts from one value to the other at the rate
expressed by the Ramp-down parameter.
The output voltage of a channel drops to zero following the Ramp-down parameter
when:
•
the channel is switched Off (
POWER
Parameter = Off);
•
the channel has tripped with 0<
TRIP
Parameter < 1000 (if the POWER-DOWN
parameter is set to RAMP);
•
the channels' outputs are disabled via the switch located on the front panel (LOC
ENABLE/DISABLE/REM ENABLE switch).
It can be programmed either via Local or Remote Control.
4.4.11
VMON
Voltage Monitored value.
It can be monitored either via Local or Remote Control.