Installation date:
...... / ...... / ..........
Fitter:
Customer:
Model:
OBSERVE: THE SETTINGS 1-8 MAY BE CHANGED BY THE CUSTOMER
& THE SETTINGS 9-19 ONLY BY THE BWT SERVICE.
7.1 Form for set values of BWT bestaqua 14, 18
Fitter:
Parameter:
Value set at installation: Description:
DATE:
[Day / month / year]
Current date
TIME:
[Hours : minutes]
Current time
LANGUAGE:
Language selection Active
language: English
START PRESSURE:
bar
Pmin
=
2.0 bar
STOP
PRESSURE:
bar
Pmax =
3.0 bar
STOP TIME DELAY:
seconds
Default setting: 10 s
CONDUCTIVITY LIMIT:
μS/cm
Default setting: 500 μS/cm
CONDUCTIVITY
ALARM:
DISABLED
/ALARM
Default setting: ALARM enabeld
WCF set point:
Range: 20 ... 79 %
Default setting: 50 %
WCF MIN:
Range: 20 ... 59 %
Default setting: 40 %
WCF MAX:
Range: 59 ... 79 %
Default setting: 60 %
PRESSURE START MAX:
Range: 1.0 ... 7.0 bar
Default setting: 2.0 bar
PRESSURE STOP MAX:
Range: 1.0 ... 7.0 bar
Default setting: 4.0 bar
STOP TIME DELAY:
Range: 0 ... 19 s
Default setting: 10 s
MAX PUMP PRESSURE:
Range: 8 ... 13 bar
Default setting: 9 bar
RINSING TIME: Range: 0 ... 599 s
Default setting: 10 s
WATER FILLING TIME:
Range: 0 ... 99 s
Default setting: 10 s
AUTOMATIC RINSING:
ENABLE / DISABLE
Default setting: ENABLE
RINSING HOUR:
TIME: 23:30 - 3:00
Default setting: 02:00 a.m.