ConneX1 Operator’s Manual
27
Manual Calibration Procedure
value(s) that are set for the detector.
2.
Connect the calibration hose to the 0.5 l/min regulator on the gas cylinder.
3.
Connect the calibration hose to the intake inlet on the calibration cap.
Begin the calibration or bump test procedure. Do not attach the calibration
cap until instructed to apply gas.
4.
When instructed, place the calibration cap on the detector
When calibration is complete, turn off the gas, and disconnect the hose from the
calibration cap and the regulator. Remove the calibration cap from the detector.
9.3.2 Calibration Gas Concentration
Refer to the table below for recommended gas concentrations for calibrations:
Table 7. Recommended Calibration Gas Concentration
Gas Type
Allowable Range
L
)E )EE
>* !
C) )E
:L*
CFM /
#!! L
) KE
9.4 Manual Calibration Procedure
To cancel calibration at any time, press .
1.
From normal operation, press to enter Configuration Mode. Press
to select
Calibration
.
2.
In the Calibration menu, scroll down and select
Calibration
.
3.
The detector zeroes the sensor before the calibration.
4.
When the zero calibration is complete, attach the calibration cap and apply
the calibration gas at a flow rate of 0.25-0.50 L/min.
If Cal IR Lock is enabled, the following screen displays to indicate calibration
can only be performed using an IR device (IntelliDoX or IR Link Adapter).
5.
Once the detector has detected a sufficient amount of gas, the detector
Содержание CONNEX1
Страница 1: ...Gas Detector Operator s Manual...
Страница 2: ......
Страница 7: ...ConneX1 Operator s Manual v...
Страница 8: ...ConneX1 Operator s Manual vi...
Страница 9: ...ConneX1 Operator s Manual vii...
Страница 71: ......
Страница 72: ...D6657 0 50104992 032 BW Technologies by Honeywell 2012 All Rights reserved...