The figure 25.1 shows the indication (FLt-E) corresponding to entry stage of the 
damping filter menu. Press the 

ENTER

 key to acceed this menu.  

 

ENTER

 To access to program the filter level. 
 To skip over this menu and go to next one. 

ESC

 To exit from the programming mode without saving changes. 

25

The damping filter cuts off input values exceeding from the limits of a simmetrical band. This band becomes more selective as the 
filter level is increased. 

The filtering level is programmable from 0 to 9. Level 0 disables the filter. 

MENU 2B - DAMPING FILTER 

[25.1]  Damping filter 

The figure 25.2 shows the initially selected level for the filter-E (any number between 
0 and 9) with the FLT LED activated. 
Press repeatedly the 

key to change the digit until desired value appears on the 

display. 
 

ENTER

 To save the entry into the memory and go to the next programming menu. 

ESC

 To exit from the programming mode without saving changes. 

[25.2]  Filter value 

B

A

   TARE

HOLD

LIMIT

MAX

MIN

DATA

DSP2

INP2

 FLT

STORE

DSP1

  INP1

2

1

4

3

  TARE

RESET

LIMIT

MAX/MIN

ENTER

ESC

DATA

PROG

TEACH

PRG

RUN

B

A

   TARE

HOLD

LIMIT

MAX

MIN

DATA

DSP2

INP2

 FLT

STORE

DSP1

  INP1

2

1

4

3

  TARE

RESET

LIMIT

MAX/MIN

ENTER

ESC

DATA

PROG

TEACH

PRG

RUN

 

The 9181 model of DIGIMASTER series done with new 
technologies and giving high performances like: display 
range of ±9999 points, up to 30 points of linearization, 
direct access to the setpoint programming, 31 
programmable logical functions and high conversion 
rate @ 555 / second.
 

 

The 9181 is an instrument to measure and control with direct 
indication in engineering units. The multifunction input board 
allows to connect Load-Cells (mV) or Shunts to measure DC 
currents, Process signals ±10V or ±20mA or lineal 
potentiometer for measure distance, length etc.. The 

 

instrument supply different excitation voltages for sensors, 
24V @ 30mA, 2.2V @ 30mA, 5 or 10V  @ 120mA allowing 
supply up to 4 Load-Cells; This differents voltages are 
selected by internal jumpers. 
Thanks to its high conversion rate (555/s) can read peaks or 
valley values from signal with a minimum width of 2,1 ms. An 
analog output (ANA option) transmitting 200 readings per 
second, an optocouplers output option (4OP o 4OPP) with a 
reaction time of 2,1 ms or 2 relay or 4 relay as well as the 
easy link to a PC through RS2 or RS4 serial output option 
using protocolos burster, ISO1745 or MODBUS RTU with the  
possibility of using a logical function that sends through RS  
200 informations of variable per second. All is conferring to 
the instrument very high performances. 

In adition the instrument has three kind of filters that allow to 
stabilize the reading with signals comming from differents 
process.  
A special function nr27 SAMPLE & HOLD allows to stop 
during hold time the reached value during the measure as well 
as the PEAK, VALLEY, PEAK-PEAK values and also the 
comparison with  SETPOINTS (selectable). 
The basic instrument is made with main board, supply filter, 
input board and display    (see figure on page. 4). 
The basic functions of the instrument are display of input 
variables value, reading and store of peak,valley and peak-
peak of this variables as well as funtions Hold, Tare and reset 
of them. The model 9181 also accept the following output 
options: 
COMUNICATION 
 RS2 

Serie 

RS232C 

 RS4 

Serie 

RS485 

CONTROL 
 

ANA 

analog output 4-20mA, 0-10V 

 

2RE 

2 Relais SPDT 8A 

 

4RE 

4 Relais SPST 0.2A 

 

4OP 

4 output OPTOS  NPN 

 

4OPP 

4 output OPTOS  PNP 

All outputs are optoisolated from input signal and general 

power supply. 

1. MODEL 9181

5

This instrument conforms to the following directives: 89/336/CEE and 73/23/CEE 

Caution: Read complete instructions to ensure safety protections. 

Содержание 9181

Страница 1: ...span are 9999 and 9999 points a To validate data and advance to the next point press ENTER or b To save the programmed data in the memory and return to the run mode the meter is scaled by three point...

Страница 2: ...E DSP1 INP1 2 1 4 3 TAR E R E SE T LIMIT MAX MIN E NTE R E SC DATA PROG TE ACH PR G R UN 2 INTRODUCTION TO THE DIGIMASTER This manual does not constitute a formal agreement All information given in th...

Страница 3: ...ond the indication P 30 appears in the display 3 23 23 2 Input 30 value B A TAR E HO LD LIMIT MAX MIN DATA DSP2 INP2 FLT STO R E DSP1 INP1 2 1 4 3 TAR E R E SE T LIMIT MAX MIN E NTE R E SC DATA PROG T...

Страница 4: ...lter The figure 24 2 shows the initially selected level for the filter P any number between 0 and 9 with the FLT LED activated Press repeatedly the key to change the digit until desired value appears...

Страница 5: ...mA or lineal potentiometer for measure distance length etc The instrument supply different excitation voltages for sensors 24V 30mA 2 2V 30mA 5 or 10V 120mA allowing supply up to 4 Load Cells This dif...

Страница 6: ...values 26 This menu allows selection among 4 levels of display rounding When resolution is not critical a rounding increment higher than 1 may help to stabilize the display MENU 2AB ROUND FILTER Progr...

Страница 7: ...Indicates exit from de program mode with data memory storage 27 This menu allows enabling and disabling the tare function and its reset MENU 2 TARE The initially programmed option appears on the displ...

Страница 8: ...value different from zero is contained in the tare memory To reset the tare memory press and hold down the RESET key then press the TARE key Release first TARE then RESET To take a tare or reset it ba...

Страница 9: ...d VALEY distance value detected since the last reset or tare B A TAR E HO LD LIMIT MAX MIN DATA DSP2 INP2 FLT STO R E DSP1 INP1 2 1 4 3 TAR E R E SE T LIMIT MAX MIN E NTE R E SC DATA PROG TE ACH PR G...

Страница 10: ...m wiring connections remove the terminal block from the meter s connector strip the wire leaving from 7 to 10 mm exposed and insert it into the proper terminal while pushing the fingertip down to open...

Страница 11: ...performed on a falling edge applied to the pin with respect to COMMON Low level The function remains activated while the corresponding pin is held at a low level with respect to COMMON Default factory...

Страница 12: ...scription Activation 13 ANA GROSS Makes the analog output follow the gross value measured value tare Fixed level 14 ZERO ANA Puts the analog output to the zero state 0 V for 0 10 V 4 mA for 4 20 mA Fi...

Страница 13: ...med with the MENU 3B the first digit to 1 or 2 and fourth digit to 0 During the HOLD s time on display is possible to show the stored values net gross valley peak or peak peak via keyboard or the spec...

Страница 14: ...alue in memory and goes to next step ESC Cancel programming and goes to run mode Reset peak and valley values Restart the measuring and output operation Restart the setpoints operation if 26 was OFF 1...

Страница 15: ...LD LIMIT MAX MIN DATA DSP2 INP2 FLT STO R E DSP1 INP1 2 1 4 3 TAR E R E SE T LIMIT MAX MIN E NTE R E SC DATA PROG TE ACH PR G R UN B A TAR E HO LD LIMIT MAX MIN DATA DSP2 INP2 FLT STO R E DSP1 INP1 2...

Страница 16: ...djust 5V Exc 10V DC J5 J1 P2 fine adjust 10V Default setting Exc 10V P2 adjust 10V P1 adjust 5V WARNING J3 J4 J5 connect only one P1 Connection type potentiometer with Input impedance 10M POT Excitati...

Страница 17: ...is shipped from the factory with a safety code of 0000 Once introduced this code you are asked to select whether to change it or to enter directly in the parameter lockout list If you decide to chang...

Страница 18: ...PROG TE ACH PR G R UN B A TAR E HO LD LIMIT MAX MIN DATA DSP2 INP2 FLT STO R E DSP1 INP1 2 1 4 3 TAR E R E SE T LIMIT MAX MIN E NTE R E SC DATA PROG TE ACH PR G R UN B A TAR E HO LD LIMIT MAX MIN DAT...

Страница 19: ...MIT MAX MIN DATA DSP2 INP2 FLT STO R E DSP1 INP1 2 1 4 3 TAR E R E SE T LIMIT MAX MIN E NTE R E SC DATA PROG TE ACH PR G R UN 19 1 Scale configuration In this menu will be intoduced the necessary para...

Страница 20: ...INP2 FLT STO R E DSP1 INP1 2 1 4 3 TAR E R E SE T LIMIT MAX MIN E NTE R E SC DATA PROG TE ACH PR G R UN 20 3 Display 2 value B A TAR E HO LD LIMIT MAX MIN DATA DSP2 INP2 FLT STO R E DSP1 INP1 2 1 4 3...

Страница 21: ...span are 9999 and 9999 points a To validate data and advance to the next point press ENTER or b To save the programmed data in the memory and return to the run mode the meter is scaled by three point...

Страница 22: ...E DSP1 INP1 2 1 4 3 TAR E R E SE T LIMIT MAX MIN E NTE R E SC DATA PROG TE ACH PR G R UN 2 INTRODUCTION TO THE DIGIMASTER This manual does not constitute a formal agreement All information given in th...

Страница 23: ...ond the indication P 30 appears in the display 3 23 23 2 Input 30 value B A TAR E HO LD LIMIT MAX MIN DATA DSP2 INP2 FLT STO R E DSP1 INP1 2 1 4 3 TAR E R E SE T LIMIT MAX MIN E NTE R E SC DATA PROG T...

Страница 24: ...lter The figure 24 2 shows the initially selected level for the filter P any number between 0 and 9 with the FLT LED activated Press repeatedly the key to change the digit until desired value appears...

Страница 25: ...mA or lineal potentiometer for measure distance length etc The instrument supply different excitation voltages for sensors 24V 30mA 2 2V 30mA 5 or 10V 120mA allowing supply up to 4 Load Cells This dif...

Страница 26: ...values 26 This menu allows selection among 4 levels of display rounding When resolution is not critical a rounding increment higher than 1 may help to stabilize the display MENU 2AB ROUND FILTER Progr...

Страница 27: ...Indicates exit from de program mode with data memory storage 27 This menu allows enabling and disabling the tare function and its reset MENU 2 TARE The initially programmed option appears on the displ...

Страница 28: ...value different from zero is contained in the tare memory To reset the tare memory press and hold down the RESET key then press the TARE key Release first TARE then RESET To take a tare or reset it ba...

Страница 29: ...d VALEY distance value detected since the last reset or tare B A TAR E HO LD LIMIT MAX MIN DATA DSP2 INP2 FLT STO R E DSP1 INP1 2 1 4 3 TAR E R E SE T LIMIT MAX MIN E NTE R E SC DATA PROG TE ACH PR G...

Страница 30: ...m wiring connections remove the terminal block from the meter s connector strip the wire leaving from 7 to 10 mm exposed and insert it into the proper terminal while pushing the fingertip down to open...

Страница 31: ...performed on a falling edge applied to the pin with respect to COMMON Low level The function remains activated while the corresponding pin is held at a low level with respect to COMMON Default factory...

Страница 32: ...scription Activation 13 ANA GROSS Makes the analog output follow the gross value measured value tare Fixed level 14 ZERO ANA Puts the analog output to the zero state 0 V for 0 10 V 4 mA for 4 20 mA Fi...

Страница 33: ...med with the MENU 3B the first digit to 1 or 2 and fourth digit to 0 During the HOLD s time on display is possible to show the stored values net gross valley peak or peak peak via keyboard or the spec...

Страница 34: ...alue in memory and goes to next step ESC Cancel programming and goes to run mode Reset peak and valley values Restart the measuring and output operation Restart the setpoints operation if 26 was OFF 1...

Страница 35: ...LD LIMIT MAX MIN DATA DSP2 INP2 FLT STO R E DSP1 INP1 2 1 4 3 TAR E R E SE T LIMIT MAX MIN E NTE R E SC DATA PROG TE ACH PR G R UN B A TAR E HO LD LIMIT MAX MIN DATA DSP2 INP2 FLT STO R E DSP1 INP1 2...

Страница 36: ...djust 5V Exc 10V DC J5 J1 P2 fine adjust 10V Default setting Exc 10V P2 adjust 10V P1 adjust 5V WARNING J3 J4 J5 connect only one P1 Connection type potentiometer with Input impedance 10M POT Excitati...

Страница 37: ...is shipped from the factory with a safety code of 0000 Once introduced this code you are asked to select whether to change it or to enter directly in the parameter lockout list If you decide to chang...

Страница 38: ...PROG TE ACH PR G R UN B A TAR E HO LD LIMIT MAX MIN DATA DSP2 INP2 FLT STO R E DSP1 INP1 2 1 4 3 TAR E R E SE T LIMIT MAX MIN E NTE R E SC DATA PROG TE ACH PR G R UN B A TAR E HO LD LIMIT MAX MIN DAT...

Страница 39: ...MIT MAX MIN DATA DSP2 INP2 FLT STO R E DSP1 INP1 2 1 4 3 TAR E R E SE T LIMIT MAX MIN E NTE R E SC DATA PROG TE ACH PR G R UN 19 1 Scale configuration In this menu will be intoduced the necessary para...

Страница 40: ...INP2 FLT STO R E DSP1 INP1 2 1 4 3 TAR E R E SE T LIMIT MAX MIN E NTE R E SC DATA PROG TE ACH PR G R UN 20 3 Display 2 value B A TAR E HO LD LIMIT MAX MIN DATA DSP2 INP2 FLT STO R E DSP1 INP1 2 1 4 3...

Страница 41: ...a 30V DC F2A 250V 5 TECHNICAL SPECIFICATONS 41 Process input Input voltage pin2 versus pin 3 0 5 0 10 V Input impedance 1M Input voltage input pin1 versus pin 3 0 1V Input impedance 100M Input current...

Страница 42: ...94 V 0 Reaction time Peak value capture Input signal minimal time 2 1ms Reaction time Hold Display Max 10ms Hold Analoge Max 10ms Hold RS Max 10ms Logical Input All Max 10ms 42 Maximum and minimum inp...

Страница 43: ...he case and slide them over the guide tracks until they touch the panel at the rear side Press slightly to fasten the bezel to the panel and secure the clips To take the instrument out of the panel pu...

Страница 44: ...the warranty period please contact the distributor from whom you purchased the product This warranty does not apply to defects resulting from action of the buyer such as mishandling or improper interf...

Страница 45: ...ITY Applicable Standars EN50081 1 Generic emission EN55022 CISPR22 Class B Applicable Standars EN50082 1 Generic immunity IEC1000 4 2 Level 3 Criteria B Air Discharge 8kV Contact Discharge 6kV IEC1000...

Страница 46: ...47 OUTPUT OPTIONS RELAIS OPTOS ANNEX Valid only for 9181 See Vxxx1 Vxxx2 Vxxx3 Vxxx4 manual 53 ANALOG OUTPUT ANNEX Valid only for 9181 See Vx1xx manual...

Страница 47: ...ion in 9181 47 Menu 3B 48 Direct programming of the setpoint value 49 Output reaction time 50 TECHNICAL SPECIFICATIONS Reaction time 5ms with Filter off Cut Frequence 10Hz with Filter off Conversions...

Страница 48: ...ammed in the MENU 3B the first digit to 1 or 2 and the fourth digit to 0 When there is positive overflow OVFLO or negative overflow OVFLO The output goes to repose mode depending on the programming of...

Страница 49: ...to peak value Digit 5 0 Normaly open 1 Normaly closed NEW FUNCTIONS burster ISO FUNCTION Answer type I 0I Transmits logical input status Y 0Y Transmits Peak to peak value Returns value n 0n LATCH rela...

Страница 50: ...ng mode PROG and by pressing LIMIT key access to the setpoint 1 value The setpoints value appears at each press of ENTER key The led indicating the setpoint number turns on and the value in the main d...

Страница 51: ...100 Output reaction time 4OP 4OPP 2 1ms OPTO output Input 90 0 Setpoint 52 This time is with the 4OP or 4OPP option without filter and with the fast option in the setpoint programming see page 50...

Страница 52: ...47 OUTPUT OPTIONS RELAIS OPTOS ANNEX Valid only for 9181 See Vxxx1 Vxxx2 Vxxx3 Vxxx4 manual 53 ANALOG OUTPUT ANNEX Valid only for 9181 See Vx1xx manual...

Страница 53: ...ion in 9181 47 Menu 3B 48 Direct programming of the setpoint value 49 Output reaction time 50 TECHNICAL SPECIFICATIONS Reaction time 5ms with Filter off Cut Frequence 10Hz with Filter off Conversions...

Страница 54: ...ammed in the MENU 3B the first digit to 1 or 2 and the fourth digit to 0 When there is positive overflow OVFLO or negative overflow OVFLO The output goes to repose mode depending on the programming of...

Страница 55: ...to peak value Digit 5 0 Normaly open 1 Normaly closed NEW FUNCTIONS burster ISO FUNCTION Answer type I 0I Transmits logical input status Y 0Y Transmits Peak to peak value Returns value n 0n LATCH rela...

Отзывы: