Burnham 4FHL-107A Скачать руководство пользователя страница 9

9

The unit should be located in the boiler room 

so as to provide ease of venting and adequate 

clearance for maintenance, serviceability and 

installation of piping. 
The tube pull space listed in the Burnham 

Commercial product catalog must be provided 

at the front of the boiler. The coil pull space must 

be maintained at the front of units equipped with 

tankless coils. Floor construction should have 

adequate load bearing characteristics to bear 

the weight of the boiler filled with water. A boiler 

foundation is recommended if the boiler room 

floor is weak, uneven or if a water condition 

exists. These boilers are not for installation on 

combustible flooring. 

B.   Installation Clearance

 

Minimum clearances to combustible walls shall 

be as follows: 

1.  Models 4FH-63A thru 180: 6

"

 sides, rear and 

above

  2.  Models 4FH-209A thru 3075A: 18

"

 sides, rear, 

and above

  3.  Minimum recommended service clearances: 

18

".

 

See boiler submittal drawings for tube pull 

clearance requirements. 
If desiccant package was ordered, be sure 

to remove from the boiler furnace using the 

rear access, and from the waterside using the 

manhole cover.

4.  FLUE OUTLET, STACK, AND BREECHING

 

 The maximum weight limit on the boiler flue outlets 

is as follows: 
1. Series 4FH: 250 lb 
2.  

All stack/economizer weights exceeding the limits 

above will need to be independently supported.

 

Stack design: The stacks shall be installed in 

 

compliance with NFPA 54, ANSI Standard 

 

Z223.1, state and local codes, using a category 

 

III product for positive, non-condensing 

 

appliances. The boiler flue outlets are generally

 

 

sized for the correct stack diameter, but there 

 

are exceptions to this.

 

 The 4FH Series boilers are equipped with a flue 

outlet stub to accept a slip-on stack connection.

 

 The boilers are optimally designed to run with a flue 

outlet pressure of .10-.30”wc pressure. The stack 

design, taking into account the draft effect and all 

friction losses, should arrive at 0.0

"

wc +/- .10

"

wc 

pressure at the inlet. Horizontal runs should be kept 

to a minimum. This will ensure the boiler will meet 

the maximum capacity, and will light off and have 

stable and consistent combustion.

 

 On installations where a natural draft stack is used, 

causing high breeching drafts, the boiler locking 

blade damper (on boilers equipped with one) may 

require adjusting, or one may need to be installed at 

the boiler breeching. In multiple boiler installations, 

or in installations where the breeching draft may vary 

considerably, automatic draft controls in combination 

with a motorized damper may be required.

5.  COMBUSTION AIR REQUIREMENTS

 

All boiler rooms must be adequately vented to 

provide enough combustion air to the boiler for proper 

tuning and operation, to prevent oxygen depletion, 

possible carbon monoxide formation, possible 

accumulation of fuel fumes, and possible equipment 

explosions. A free flow of combustion air will aid the 

proper operation of the burner and allow for proper 

venting of the boiler. The instructions below must be 

followed to properly size make-up air openings in the 

boiler room. Consult NFPA-54 National Fuel Gas Code, 

NFPA-31 Installation of Oil Burning Equipment for more 

detailed explanations, and local codes for additional 

guidance for boiler rooms below grade and other  

specific situations.

Two general methods may be used:

 

1.   When one permanent opening is used: The 

opening shall commence within 12

"

 of the top 

of the enclosure (boiler room) and the opening 

shall communicate directly with the outdoors, 

or through a vertical or horizontal duct with the 

outdoors. The opening shall have a minimum 

free area of 1 sq in per 3,000 BTU/hr total input 

of all equipment in the enclosure, and not less 

than the sum of the areas of all equipment vent 

connectors.

 

2.   When two permanent openings are used: One 

opening location shall begin within 12

"

 of the 

top of the enclosure, and the other opening 

location shall begin within 12

"

 of the bottom of 

the enclosure. When communication is directly 

with the outdoors, or through vertical ducts, each 

opening shall have a minimum free area of 1 sq 

in per 4,000 BTU/hr total input of all equipment 

in the enclosure. Where communicating with the 

outdoors through horizontal ducts, each opening 

shall have a minimum free area of 1 sq in per 

2,000 BTU/hr total input of all equipment in the 

enclosure.

Содержание 4FHL-107A

Страница 1: ...hnician BEFORE installing read all instructions in this manual and all other information shipped with the boiler Post all instructions and manuals near the boiler for reference by service personnel Pe...

Страница 2: ...es having jurisdiction should be consulted before installations are made C All wiring on boilers installed in Canada shall be made in accordance with the Canadian Electrical Code and or Local Regulati...

Страница 3: ...ne Burner boiler systems produce steam or hot water in a pressurized vessel by mixing extremely flammable gaseous liquid or solid fuels with air to produce combustion and very hot products of combusti...

Страница 4: ...e s ret sont absents ou install s l aide de cavaliers Ne pas faire fonctionner si une commande un interrupteur un composant ou un dispositif est entr en contact avec de l eau Improper installation adj...

Страница 5: ...e combustible contiennent de l alumine de la silice des m taux lourds du monoxyde de carbone des oxydes d azote des ald hydes ou d autres substances toxiques ou dangereuses pouvant causer la mort ou d...

Страница 6: ...ted piping electrical and control systems used and maintained in the boiler room Le terme syst me de br leur chaudi re utilis dans ce manuel signifie tout quipement m canique ou lectrique y compris la...

Страница 7: ...esting Controls 16 17 Initial Cleaning Steam Boilers 17 Initial Cleaning Water Boilers 17 18 Water Boiler Operation 18 Boiler Water Treatment 18 pH or Alkalinity Test 18 Warnings about Frequent Water...

Страница 8: ...ombustion efficiency of over 80 This manual gives the necessary information for the proper installation operation maintenance and service of units For special installation problems contact Burnham Com...

Страница 9: ...um capacity and will light off and have stable and consistent combustion On installations where a natural draft stack is used causing high breeching drafts the boiler locking blade damper on boilers e...

Страница 10: ...altitude installations above 1 000 ft An adjustment of 3 5 per 1 000 ft of elevation is recommended 6 LOCATION OF ASME STAMPING DATA The ASME stamping data is located as follows 1 Series 4FH Sizes 63...

Страница 11: ...the boiler warms up If formation of condensate persists the low limit should be adjusted upward until condensate no longer forms Water boilers and low pressure steam boilers must have a set LFH at 12...

Страница 12: ...es in the boiler metal These stresses can cause damage to the boiler by loosening tubes or in more severe instances can crack tube sheet ligaments furnaces or waterlegs B If temperature differentials...

Страница 13: ...MANUAL 9 RELIEF VALVES Boiler relief valves are normally shipped loose and have been properly sized for your boiler The aggregate capacity of the relief valves as stamped on the valve rating plates mu...

Страница 14: ...14 FIGURE 4 TS 71 130 D INSTALLATION INSTRUCTIONS FIGURE 3 TS 71 176 B...

Страница 15: ...15 TS 71 131 D FIGURE 5 TS 3 101 4 INSTALLATION INSTRUCTIONS FIGURE 6...

Страница 16: ...control Avant que l installation de la chaudi re soit consid r e comme termin e v rifier le fonctionnement de ses dispositifs de contr le en particulier les interrupteurs bas niveau d eau et le contr...

Страница 17: ...afety relief valve using extreme care to avoid damaging it A Check Operating Control Raise and lower operating control setting as required to start and stop burner B Warning Check High Limit Control J...

Страница 18: ...WATER TREATMENT Boiler water treatment will help maximize the effectiveness and prolong the life of pressure vessels The general objectives of boiler water treatment are A Remove corrosive gases from...

Страница 19: ...chaudi re par l oxyg ne provoque la corrosion des composants en fer et en acier et peut mener une d faillance La garantie standard de Burnham ne couvre pas les probl mes caus s par la contamination de...

Страница 20: ...emperature to increase even if the gauge pressure is 0 It is better to allow the entire system to cool gradually never force cool the boiler as damage can also be inflicted due to thermal shock G When...

Страница 21: ...rbulator replacement is from the front smokebox Turbulators should be installed and removed from the front of the boiler only Series 4FH All 4FH Series boilers come equipped with turbulators in all th...

Страница 22: ...to solder joints on bellows and float when this type of control is used Check the float for evidence of collapse and check mercury bulb where applicable for mercury separation or discoloration DO NOT...

Страница 23: ...at the end of heating season Drain off boiler water until it runs clear while holding the boiler temperature between 180 and 200 F Then refill to top of gauge glass B Water Boilers Since a water boile...

Страница 24: ...ion Safety Controls Flame Failure Weekly Operator If flame display installed read and log for both pilot and main flames notify service organization if readings are very high very low or fluctuating r...

Страница 25: ...ition Interlock Annually Service Technician Refer to burner instructions Low Fire Start Interlock Annually Service Technician Refer to burner instructions Automatic Changeover At Least Annually Servic...

Страница 26: ...26...

Страница 27: ...27...

Страница 28: ...Product under conditions varying materially from those under such Products is usually tested under industry standards as of the shipment time C Any damage to the Product due to abrasion erosion corro...

Отзывы: