See item 10 under Operating Instruction if it becomes 

necessary to add water to the boiler more frequently 

than once a month.

 

Se reporter à l’article 10 dans la section Instructions 

de fonctionnement si le remplissage de la chaudière 

devient nécessaire plus d’une fois par mois.

 

1.   GENERAL
 

Inspection should be conducted annually. Service 

as frequently as specified in paragraphs below. Before 

service or maintenance is performed complete boiler 

shutdown/cooldown procedure.

2.   BOILER SHUT DOWN AND COOLDOWN    

 

 PROCEDURE
    NOTE:

 This procedure is generally required in 

preparation for corrective or preventative maintenance 

in the unit. This procedure must be supervised by an 

individual who is thoroughly qualified in operation and 

maintenance of the equipment at hand. This is written 

with Steam Boilers in mind, but the principles are 

applicable to Hot Water Boilers as well.

A.

  Decrease plant load as much as possible.

B.

  Turn boiler switch off. If control power from  

burner is used to support accessories, leave 

on until boiler system has cooled down.

C. 

 Shut and lock manual gas and oil valves as  

applicable.

D.

  In single boiler installations, some small steam  

loads can remain on to assist in a controlled  

cooldown of the boiler (i.e., deaerator). In multiple  

boiler installations, shut down the non-return 

valve and the back up valve. Lock them shut.

E.

 Allow the boiler feed pump to remain active. As 

the boiler cools down, the water level is reduced 

by demand or shrinkage. It is best to be aware of 

the boiler level at all times.

F.

  When boiler pressure has decreased to 5 to 

10 psi on the pressure gauge, open the boiler 

manual vent valve on the top of the boiler. This 

is to act as a sentinel against the increase in 

pressure and to prevent the boiler from going into 

a vacuum. Lock the valve open.

 NOTE: 

Depending on the size of the boiler, the large 

mass of heating surfaces that are still hot can cause the 

boiler water temperature to increase, even if the gauge 

pressure is “0”. It is better to allow the entire system to 

cool gradually, never force cool the boiler as damage 

can also be inflicted due to “thermal shock.”

G.

  When boiler and water are below 120°F, shut off    

power to the unit and lock out the circuit    

 

breakers. 

H.

  If required, open front and rear doors for   

 

observation of fireside surfaces. 

I.

  Drain boiler down as far as required. (Usually  

completely.) Make sure the vent valve on the top 

of the boiler remains open. Open and lock the 

float control low water cutoff drain valves. These 

will serve as additional vents.

J.

  Shut and lock the boiler feed valves, and any  

 

blowdown valves that can be affected by other  

boilers in the same facility (i.e., bottom blow down 

valves can tie into a common blowdown 

separator in a multiple boiler installation).

K.

  If necessary to remove handhole and/or manhole  

plates for water side inspection or maintenance,  

use extreme caution. Loosen the nuts securing 

the arch enough to allow the plate to drop  

approximately 1/8 inch when tapped loose with    

a mallet. Once again, ensure the pressure in the    

boiler is “0” before loosening the plate. Remove  

the plate the remainder of the way. Wear gloves    

and eye protection at all times. 

3.   CLEAN THE BOILER HEATING SURFACES  

 

AND FLUE  

 

 

At least once each year, preferably at the end of the 

heating season.

A.  Clean the Vent System

Vent system should be checked annually for:
1. Obstructions.
2.  Accumulations of soot.
3.  Deterioration of vent pipe or vent accessories   

due to condensation or other reasons. 

4.  Proper support no sags, particularly in 

horizontal runs.

5.  Tightness of joints.

 

Remove all accumulations of soot with a wire 

brush and vacuum. Remove all obstructions. Replace 

deteriorated parts and support properly. Seal all joints.

B.  Clean the Boiler Heating Surfaces

   At the end of the heating season, clean boiler  

 

heating surfaces thoroughly. Access to boiler  

firetubes may be gained by removing the front 

and rear smokeboxes or smokebox doors.  

 

Where applicable, remove the turbulators, paying  

close attention to which tubes have turbulators.  

SECTION IV  — SERVICE INSTRUCTIONS

Содержание 4FHL-107A

Страница 1: ...hnician BEFORE installing read all instructions in this manual and all other information shipped with the boiler Post all instructions and manuals near the boiler for reference by service personnel Pe...

Страница 2: ...es having jurisdiction should be consulted before installations are made C All wiring on boilers installed in Canada shall be made in accordance with the Canadian Electrical Code and or Local Regulati...

Страница 3: ...ne Burner boiler systems produce steam or hot water in a pressurized vessel by mixing extremely flammable gaseous liquid or solid fuels with air to produce combustion and very hot products of combusti...

Страница 4: ...e s ret sont absents ou install s l aide de cavaliers Ne pas faire fonctionner si une commande un interrupteur un composant ou un dispositif est entr en contact avec de l eau Improper installation adj...

Страница 5: ...e combustible contiennent de l alumine de la silice des m taux lourds du monoxyde de carbone des oxydes d azote des ald hydes ou d autres substances toxiques ou dangereuses pouvant causer la mort ou d...

Страница 6: ...ted piping electrical and control systems used and maintained in the boiler room Le terme syst me de br leur chaudi re utilis dans ce manuel signifie tout quipement m canique ou lectrique y compris la...

Страница 7: ...esting Controls 16 17 Initial Cleaning Steam Boilers 17 Initial Cleaning Water Boilers 17 18 Water Boiler Operation 18 Boiler Water Treatment 18 pH or Alkalinity Test 18 Warnings about Frequent Water...

Страница 8: ...ombustion efficiency of over 80 This manual gives the necessary information for the proper installation operation maintenance and service of units For special installation problems contact Burnham Com...

Страница 9: ...um capacity and will light off and have stable and consistent combustion On installations where a natural draft stack is used causing high breeching drafts the boiler locking blade damper on boilers e...

Страница 10: ...altitude installations above 1 000 ft An adjustment of 3 5 per 1 000 ft of elevation is recommended 6 LOCATION OF ASME STAMPING DATA The ASME stamping data is located as follows 1 Series 4FH Sizes 63...

Страница 11: ...the boiler warms up If formation of condensate persists the low limit should be adjusted upward until condensate no longer forms Water boilers and low pressure steam boilers must have a set LFH at 12...

Страница 12: ...es in the boiler metal These stresses can cause damage to the boiler by loosening tubes or in more severe instances can crack tube sheet ligaments furnaces or waterlegs B If temperature differentials...

Страница 13: ...MANUAL 9 RELIEF VALVES Boiler relief valves are normally shipped loose and have been properly sized for your boiler The aggregate capacity of the relief valves as stamped on the valve rating plates mu...

Страница 14: ...14 FIGURE 4 TS 71 130 D INSTALLATION INSTRUCTIONS FIGURE 3 TS 71 176 B...

Страница 15: ...15 TS 71 131 D FIGURE 5 TS 3 101 4 INSTALLATION INSTRUCTIONS FIGURE 6...

Страница 16: ...control Avant que l installation de la chaudi re soit consid r e comme termin e v rifier le fonctionnement de ses dispositifs de contr le en particulier les interrupteurs bas niveau d eau et le contr...

Страница 17: ...afety relief valve using extreme care to avoid damaging it A Check Operating Control Raise and lower operating control setting as required to start and stop burner B Warning Check High Limit Control J...

Страница 18: ...WATER TREATMENT Boiler water treatment will help maximize the effectiveness and prolong the life of pressure vessels The general objectives of boiler water treatment are A Remove corrosive gases from...

Страница 19: ...chaudi re par l oxyg ne provoque la corrosion des composants en fer et en acier et peut mener une d faillance La garantie standard de Burnham ne couvre pas les probl mes caus s par la contamination de...

Страница 20: ...emperature to increase even if the gauge pressure is 0 It is better to allow the entire system to cool gradually never force cool the boiler as damage can also be inflicted due to thermal shock G When...

Страница 21: ...rbulator replacement is from the front smokebox Turbulators should be installed and removed from the front of the boiler only Series 4FH All 4FH Series boilers come equipped with turbulators in all th...

Страница 22: ...to solder joints on bellows and float when this type of control is used Check the float for evidence of collapse and check mercury bulb where applicable for mercury separation or discoloration DO NOT...

Страница 23: ...at the end of heating season Drain off boiler water until it runs clear while holding the boiler temperature between 180 and 200 F Then refill to top of gauge glass B Water Boilers Since a water boile...

Страница 24: ...ion Safety Controls Flame Failure Weekly Operator If flame display installed read and log for both pilot and main flames notify service organization if readings are very high very low or fluctuating r...

Страница 25: ...ition Interlock Annually Service Technician Refer to burner instructions Low Fire Start Interlock Annually Service Technician Refer to burner instructions Automatic Changeover At Least Annually Servic...

Страница 26: ...26...

Страница 27: ...27...

Страница 28: ...Product under conditions varying materially from those under such Products is usually tested under industry standards as of the shipment time C Any damage to the Product due to abrasion erosion corro...

Отзывы: