25
ITEM
FREQUENCY
ACCOMPLISHED BY
REMARKS
Atomizing Air/Steam
Annually
Service Technician
Refer to burner instructions
High and Low Gas
Monthly
Operator
Refer to burner instructions
Pressure Interlocks
High and Low Oil
Monthly
Operator
Refer to burner instructions
Pressure Interlocks
High and Low Oil
Monthly
Operator
Refer to burner instructions
Temperature Interlocks
Fuel Valve Interlock
Annually
Service Technician
Refer to burner instruction
Switch
Purge Switch
Annually
Service Technician
Refer to burner instructions
Burner Position Interlock
Annually
Service Technician
Refer to burner instructions
Low Fire Start Interlock
Annually
Service Technician
Refer to burner instructions
Automatic Changeover
At Least Annually Service Technician
Under supervision of gas utility
Control (dual fuel)
Safety Valves
As required
Operator
In accordance with procedure in
Section VI, ASME Boiler and
Pressure Vessel Code,
Recommended Rules for Care
and Operation of Heating
Boilers or Section VII for power
boilers.
Inspect Burner Components
Semi-annually
Service Technician
Refer to burner instructions
Boiler Hydro-Test
Annually
Service Technician
Performed as required, in
accordance with NBIC Part 2,
not to exceed 90% of relief
valve setting.
PERIODIC TESTING RECOMMENDED