SERVICING INSTRUCTIONS 

As with all gas appliances the unit must be serviced at least once per year, preferably at 
the  beginning  of  the  heating  season.

 

All  servicing  must  be  carried  out  by  a  qualified 

service person. 

Before commencing any servicing, ensure that the gas is turned off to the appliance and 
that the appliance is cool. 

Cleaning – If required the casing should be wiped with a cloth dampened in soapy water.  
The glass may be cleaned with any non-abrasive cleaner such as ‘hob brite‘. 

Unscrew  the  decorative  frame  to  remove.  Unscrew  the  four  screws  holding  the  glass, 
remove and place thoughtfully to avoid damage or injury. 

Carefully remove the loose chippings and remove any dirt with a soft brush (paint brush) 
and clean the burner and associated parts using a vacuum cleaner. Take particular care to 
remove all debris around the pilot light. 

We  recommend  the  use  of  a  HEPA  filtered  vacuum  to  remove  any  dust  and  soot 
accumulated  in  the  heater  before  and  after  working  on  it.    Normal  hygiene  rules  of  not 
smoking, eating or drinking in the work area should be followed. 

Disconnect the gas supply to the appliance. 

Clean around all air inlet grills removing all lint in the area of the injector and ensuring the 
pilot light aeration hole and flame head are clean. Injectors 

– 

Only original manufacturer’s 

injectors must be used, see section 1 for identification. Should the oxypilot system need 
to be replaced, the original manufacturer’s parts must be used. 

Controls – The GAS CONTROL IS FACTORY SET AND NORMALLY NEEDS NO ADJUSTMENT. 
Check for smooth operation of the gas valve.  Remove access cover & check the tightness 
of the thermocouple connection into the valve and test ignition leads.  

Examine the fire casing, the firebox and catalytic converters for obvious signs of damage 
or  degradation.  Clean  out  any  dirt  or  dust  accumulated  in  the  bottom  of  the  fire. 
Reassemble in reverse order. 

Test all joints for leaks.  

Following the instructions, re-lay the chippings (if used) and replace the glass. 

Light  the  fire  using  the  method  in  the  instructions  and  ensure  that  the  pilot  lights 
consistently  and  the  pilot  flame  envelopes  the  thermocouple.  The  pilot  should  hold  in 
after  approximately  10  seconds  &  turn  the  main  burner  on,  this  should  light  smoothly 
within 10 seconds. Ensure the valve turns down by double clicking the low flame button. 
The gas manifold pressures are factory preset using highly accurate equipment and do not 
normally need adjustment.  

Run appliance for 15 minutes, ensuring burner flames settle evenly. 

A combustion analysis check should then be carried out. Using an analyser to BS7927, first 
zero the equipment and sample the entire width of the combustion product outlet. Ratio 
of  CO/CO2  should  be  less  than  0.002  within  30  minutes.  (20ppm  CO  per  1%  CO2)    A 
reading of CO in the room centre should give a rise of less than 9ppm over ambient, peak 
reading.  The  catalyst  is  unlikely  to  need  replacement  during  the  life  of  the  heater  but  if 
the combustion is suspect, disconnect the appliance and contact the manufacturer. 

Содержание LONGITUDE

Страница 1: ...Burley Appliances Ltd Lands End Way Oakham Rutland LE15 6RB Telephone 44 0 1572 756956 Fax 44 0 1572 724390 e mail info burley co uk web www burley co uk G4530 39InstUser G20 G31 March 2019 TO OBTAIN...

Страница 2: ...valve Elbow 82 340 Elbow 92 160 Pilot SIT 9116 Seagas P451 Average measured NO2 room 119ppb 115 1ppb The inlet pressure must be within 1mBar of specification with all gas appliances in the house switc...

Страница 3: ...o convert cubic feet ft to cubic metre m divide the room volume in cubic feet by 35 3 3 6 The heater must not be installed in high rise blocks of flats unless a gas supply already exists bed sitting r...

Страница 4: ...connect the gas supply to the 8mm elbow on the fire Leak test the supply using an approved method Fires can be connected to the supply using semi rigid pipe i e copper tube also independently certifi...

Страница 5: ...on on the back of the appliance The top of the flue should also be capped off to prevent the entry of moisture etc consult building control if in any doubt 5 CLEARANCES TO COMBUSTIBLE MATERIALS AND SH...

Страница 6: ...hrough walls seal the pipe ends to prevent debris entering the pipes 6 5 The fire must be mounted minimum 200mm from floor level 6 6 Hang the appliance on the wall and fix into position 6 7 Fully purg...

Страница 7: ...on the gas access cover to the O position Undo the securing screw for the receiver holder on the right hand side of the appliance as shown below Pilot Burner Burner Outlet Battery Switch Battery Swit...

Страница 8: ...gas access cover is in the O position fit four AA 1 5V batteries into the receiver unit Fit the PP3 9V battery into the transmitter hand set Press the battery switch located on the underside of the g...

Страница 9: ...lit the igniter will stop another acoustic signal will confirm the pilot has been established if the pilot fails to establish repeat the process Due to the safe efficient nature of the fire it is not...

Страница 10: ...tery isolator switch back to the I position Press here and slide down CAUTION With the exception of battery replacement the receiver must be located in the carrier at all times 9 6 Pairing Handset to...

Страница 11: ...ine BEFORE you leave the installation If the appliance is not fitted in strict accordance with these instructions Burley cannot be held responsible for any damage caused and reserve the right to charg...

Страница 12: ...laced the original manufacturer s parts must be used Controls The GAS CONTROL IS FACTORY SET AND NORMALLY NEEDS NO ADJUSTMENT Check for smooth operation of the gas valve Remove access cover check the...

Страница 13: ...ings CHIP1000 900g CHIP1000 900g Glass GLA4530 GLA4530 USE ONLY GENUINE REPLACEMENT PARTS Parts ordered from our factory will normally take 5 7 working days to be delivered An Express service is avail...

Страница 14: ...be carried out in accordance with BS5871 Pt 4 The catalytic converter needs heat to work therefore before you start testing the fire must have been lit and burning on full for at least 15 mins There a...

Страница 15: ...e consult the relevant manufacturer Only use replacement catalyst supplied by Burley If you or the customer detects any odours from the fire please remember that the catalytic convertor is not an air...

Страница 16: ...r a reasonable period of time so that the capacity of the meter is used On low Input appliances such as our flueless this is even more critical because uncertainties can creep in It is worth measuring...

Страница 17: ...rmerly CORGI within the first year as with all gas products every gas appliances must be serviced every year The appliance has not been subject to misuse accident or repaired or fitted by anyone other...

Страница 18: ...recycling WEEE Dispose of electrical equipment in an environmentally correct manner When disposing components containing Refractory Ceramic Fibres RCF we recommend that the items are not broken up bu...

Страница 19: ...Page 19 of 20...

Страница 20: ...iglo fires are protected by UK patents 2193802 2240620 and 2256920 Other Patents Pending Burley Appliances Ltd Lands End Way Oakham Rutland LE15 6RB Tel 01572 725570 Fax 01572 724390 www burley co uk...

Отзывы: