Page 11 of 20 

10.

 

COMMISSIONING 

10.1

 

TEST THE GAS PRESSURE

. Turn the fire on full, attach a manometer to the inlet test point 

and  ensure  there  is  a  pressure  of  20mbar  (+/-  1mbar)  for  natural  gas  appliances  or 
37mbar for propane appliances. Now turn on every other gas appliance in the house and 
re-check the pressure. The pressure must still be within the tolerance of +/- 1mbar. Now 
turn  off  all  the  other  gas  appliances  and  turn  the  fire  down  to  pilot  only,  the  pressure 
must still be within the tolerance of +/- 1mbar. If it is not TRANSCO, BORD GAIS or the gas 
supplier  must  be  called  to  adjust  the  governor  to  the  house  before  the  fire  can  be 
commissioned further. 

Call outs to fires with incorrect pressures will be chargeable. 

10.2

 

Brief the customer on the operation of the appliance and give them all the instructions. 
The customer must be told of the need for regular servicing of the appliance, this will be 
at least once a year and be made aware that no rubbish is to be thrown onto the fire bed. 
The  customer  must  also  be  made  aware  that  purpose  provided  ventilation  should  be 
checked regularly and not be blocked.

 

10.3

 

If you have any questions or the fire is not operating correctly, phone the Burley help-
line BEFORE you leave the installation. 

If the appliance is not fitted in strict accordance with these instructions, Burley cannot 
be  held  responsible  for  any  damage  caused  and  reserve  the  right  to  charge  for  any 
corrective  work.  Double  check  standing  and  working  pressures  and  securely  seal  all 
relevant open chimneys and flues. 

10.4

 

Oxygen  Depletion  Pilot  System 

There  is  a  highly  sensitive  oxygen  depletion  sensor 

designed  into  the  pilot  light  and  may  not  light  first  time  or  may  extinguish  after  a  few 
minutes, please advise the customer of this. If any part of the OXY Pilot is damaged the 
entire  unit  must  be  replaced.  Do  not  attempt  to  bend  or  alter  the  flame  head, 
thermocouple or aeration hole. Use only genuine spare parts as similar looking parts from 
other  appliances  may  well  give  different  or  inferior  performance  and  could  lead  to  a 
hazard.  

10.5

 

Fireguards 

A  fireguard  is  not  supplied  with  this  appliance  and  being  wall  mounted,  the 

need for one will have to be assessed depending on the position, height from ground of 
the fire; however it is recommended that a fireguard to BS8423 is fitted if the fire is to be 
used in the presence of young children, the elderly and the infirm. 

 

10.6

 

Completion of Warranty Card. The installer section of the guarantee card must be filled 
in  fully  to  validate  the  warranty.  I.e.  pressure,  model,    room  size  and  Gas  Safe™ 
registered installer (formerly CORGI) number 

Содержание LONGITUDE

Страница 1: ...Burley Appliances Ltd Lands End Way Oakham Rutland LE15 6RB Telephone 44 0 1572 756956 Fax 44 0 1572 724390 e mail info burley co uk web www burley co uk G4530 39InstUser G20 G31 March 2019 TO OBTAIN...

Страница 2: ...valve Elbow 82 340 Elbow 92 160 Pilot SIT 9116 Seagas P451 Average measured NO2 room 119ppb 115 1ppb The inlet pressure must be within 1mBar of specification with all gas appliances in the house switc...

Страница 3: ...o convert cubic feet ft to cubic metre m divide the room volume in cubic feet by 35 3 3 6 The heater must not be installed in high rise blocks of flats unless a gas supply already exists bed sitting r...

Страница 4: ...connect the gas supply to the 8mm elbow on the fire Leak test the supply using an approved method Fires can be connected to the supply using semi rigid pipe i e copper tube also independently certifi...

Страница 5: ...on on the back of the appliance The top of the flue should also be capped off to prevent the entry of moisture etc consult building control if in any doubt 5 CLEARANCES TO COMBUSTIBLE MATERIALS AND SH...

Страница 6: ...hrough walls seal the pipe ends to prevent debris entering the pipes 6 5 The fire must be mounted minimum 200mm from floor level 6 6 Hang the appliance on the wall and fix into position 6 7 Fully purg...

Страница 7: ...on the gas access cover to the O position Undo the securing screw for the receiver holder on the right hand side of the appliance as shown below Pilot Burner Burner Outlet Battery Switch Battery Swit...

Страница 8: ...gas access cover is in the O position fit four AA 1 5V batteries into the receiver unit Fit the PP3 9V battery into the transmitter hand set Press the battery switch located on the underside of the g...

Страница 9: ...lit the igniter will stop another acoustic signal will confirm the pilot has been established if the pilot fails to establish repeat the process Due to the safe efficient nature of the fire it is not...

Страница 10: ...tery isolator switch back to the I position Press here and slide down CAUTION With the exception of battery replacement the receiver must be located in the carrier at all times 9 6 Pairing Handset to...

Страница 11: ...ine BEFORE you leave the installation If the appliance is not fitted in strict accordance with these instructions Burley cannot be held responsible for any damage caused and reserve the right to charg...

Страница 12: ...laced the original manufacturer s parts must be used Controls The GAS CONTROL IS FACTORY SET AND NORMALLY NEEDS NO ADJUSTMENT Check for smooth operation of the gas valve Remove access cover check the...

Страница 13: ...ings CHIP1000 900g CHIP1000 900g Glass GLA4530 GLA4530 USE ONLY GENUINE REPLACEMENT PARTS Parts ordered from our factory will normally take 5 7 working days to be delivered An Express service is avail...

Страница 14: ...be carried out in accordance with BS5871 Pt 4 The catalytic converter needs heat to work therefore before you start testing the fire must have been lit and burning on full for at least 15 mins There a...

Страница 15: ...e consult the relevant manufacturer Only use replacement catalyst supplied by Burley If you or the customer detects any odours from the fire please remember that the catalytic convertor is not an air...

Страница 16: ...r a reasonable period of time so that the capacity of the meter is used On low Input appliances such as our flueless this is even more critical because uncertainties can creep in It is worth measuring...

Страница 17: ...rmerly CORGI within the first year as with all gas products every gas appliances must be serviced every year The appliance has not been subject to misuse accident or repaired or fitted by anyone other...

Страница 18: ...recycling WEEE Dispose of electrical equipment in an environmentally correct manner When disposing components containing Refractory Ceramic Fibres RCF we recommend that the items are not broken up bu...

Страница 19: ...Page 19 of 20...

Страница 20: ...iglo fires are protected by UK patents 2193802 2240620 and 2256920 Other Patents Pending Burley Appliances Ltd Lands End Way Oakham Rutland LE15 6RB Tel 01572 725570 Fax 01572 724390 www burley co uk...

Отзывы: