SOLARCYL
IM/SC2
Installation details
The OSO unvented unit is designed for use with supply pressure up to 16 bar. For pressures over
16 bar an additional pressure reducing valve must be fitted in the supply pipe to the unit.
Components supplied with the unit for site fitting
(See also page 2 for component list)
*
Multibloc valve, includes pressure reducing valve, line strainer, balanced cold water take off,
(for shower or bidet only)
check and expansion valve.
*
Tundish
*
1/2''F x 15 x 15 tee piece.
*
Flexible hose.
*
3/4'' x 22mm Elbow / Drain Cock.
*
Commissioning valve, 1/2'' BSP male.
*
Motorised valve.
*
2 x 1/2'' BSP male solar sensor pockets.
Components factory fitted
*
Immersion heater.
*
Thermostats / thermal cut-out.
*
Temperature and pressure relief valve.
This manual gives detailed advice for installation and should be read carefully
prior to fitting any unvented unit.
This OSO cylinder must be installed by a competent person and be installed in
compliance with the OSO Installation and Maintenance Instructions, all current
legislation, codes of practice and regulations governing the installation of
unvented hot water cylinders in force at the date of installation.
-1-
PLEASE LEAVE THIS MANUAL WITH THE
OSO
UNIT AFTER INSTALLATION
INSTALLATION MANUAL
CAPACITY LITRES
HEIGHT
DIAMETER
WEIGHT EMPTY
MAX WEIGHT FULL
COIL RATING KW
UPPER COIL
LOWER COIL
210
1400
580
60
261
12
12
1600
580
64
303
12
26
2090
580
82
397
18
26
250
330
DIMENSION AND WEIGHTS TABLE 1
Health and Safety
Manual Handling Operations Regulations 1992 defines
manual handling as: “any transporting or supporting of
a load (including the lifting, putting down, pushing,
pulling, carrying or moving thereof) by hand or bodily
force”. The Regulations set no specific requirements
such as weight limits. However common sense still has
to be used based on an ergonomic approach for each
individual.