Standard and internal check to the device limits
The measured data are compared with the reference values previously stored. The deviation of different variable
measured,shall be within the following range:
Coil temperature (using resistance reading): within limits compatible with the lining material
Current up times: change% detected resistance coils + 10% (tolerance range)
Resistance between electrodes and common: between 0.3 and 3.0 times the reference early strength
Leakage current (insulation test): less than 0.1 mA
If the values deviate beyond these limits it is generated and displayed a coded alarm.
The alarm remains active and visible on the display until next test (max. 1 hour).