47
English
SE58
L
MENU 4 - MEASURE
10
20
30
40
50
60
0
0
2
4
6
8
10
12
14
16
18
20
22
Damping = OFF
FLOW RATE
MEASURE
FILTERS
>>>>
>>>>
IN
OUT
FL
OW
R
AT
E
(%
)
TIME (Sec)
Example with damping to OFF
Damping function (OFF). the meter follows
the trend of fast changes in flow.
Damping mode based on time (from 0.2s
to 1000s) The measure is averaged over
a number of samples determined by the
value assigned to the dampening function.
When the damping parameter is expressed
in seconds, the filter works damping the
measurement noise and sudden change
of flow rate. Increasing the parameter of
damping increases the stability of the
measurement.
10
20
30
40
50
60
0
0
2
4
6
8
10
12
14
16
18
20
22
Damping= from 0.2s to 1000s
FLOW RATE
MEASURE
FILTERS
>>>>
>>>>
IN
OUT
TIME (Sec)
FL
OW
R
AT
E
(%
)
Example with damping to 5,0sec.
This section of manual is extremely important because the correct setting of the filters allows to obtain a proper
response of the device to the measured flow rate and the specific requirements of use; as a general rule,
consider that, starting from Damping = OFF (no filter applied to the measure), successive values, introduce
increasing damping. The following diagrams show the device’s response to changes in flow rate from 0 to 100%,
using the different settings of the damping function.
The SMART is an adaptive filter that adapts automatically to most of the processes (recommended value),
making the response of the meter very ready to fast changes of flow and at the same time extremely precise
and stable for slow variations. It may be convenient to use a constant damping filter time, where there is a
pulsating flow (for example generated by peristaltic pumps). With longer times you get a mean value stable, while
with short times the measure will closely follow the flow pulses, but consequently more unstable. NOTE: If the
rechargeable battery is active, the damping could be set only in “SMART”.
(POS. 4.1) Measure Filter DaMPing
[Damping=OFF/SMART/(TIME)]
AL3
[MFDMP]
Содержание B0A1C2B1A4A0
Страница 1: ...Type SE58 L Transmitter Operating Instructions...
Страница 8: ...7 English SE58 L Dimensions 200 114 164 167 114 180 290 195...
Страница 9: ...8 English SE58 L Remote version 142 28 295 120 7 30...
Страница 11: ...10 English SE58 L DIMENSIONS STAINLESS STEEL VERSION Compact Version 171 156 186 146...
Страница 12: ...11 English SE58 L Separate Version 236 40 7 90 241 55...