MENU 7 - OUTPUTS
Function choice corresponding to digital Output 1. The functions are listed in the table below
.
Function choice corresponding to digital Output 2. The functions are listed in the table below.
(POS. 7.1) OUTput 1 Function
[Out1=XXXXXX]
AL3
[OUT1F]
(POS. 7.2) OUTput 2 Function
[Out2=XXXXXX]
AL3
[OUT2F]
FUNCTIONS FOR OUTPUTS 1 AND 2
• OFF:
DISABLE
• MAX AL. +:
MAX DIRECT FLOW RATE OUTPUT (ENERGIZED = AL. OFF)
• MIN AL. +:
MIN DIRECT FLOW RATE OUTPUT (ENERGIZED = AL. OFF)
• MAX/MIN+/-:
MAX/MIN DIRECT FLOW RATE OUTPUT (ENERGIZED = AL. OFF)
• MAX AL.-:
MAX INVERSE FLOW RATE OUTPUT (ENERGIZED = AL. OFF)
• MIN AL.-:
MIN INVERSE FLOW RATE OUTPUT (ENERGIZED = AL. OFF)
• MAX/MIN-:
MAX/MIN INVERSE FLOW RATE OUTPUT (ENERGIZED = AL. OFF)
• P.EMPTY:
EMPTY PIPE ALARM OUTPUT (ENERGIZED = AL. OFF)
• HARDWARE AL.:
SUM OF ALL ALARMS ”energized interrupted ” AND ”error input signal ”
• OVERFLOW:
OUT OF RANGE ALARM OUTPUT (ENERGIZED = FLOWRATE OK)
• ALL ALARMS:
SUM OF ALL ALARMS POSSIBLE
• EXT. COMM:
OUTPUT MAY TAKE A STATE DEPENDENT ON AN EXTERNAL CONTROL REMOTELY VIA MCP
• FLOW RATE SIGN.:
FLOW DIRECTION (ENERGIZED WHEN FLOW IS NEGATIVE)
• SCALE:
INDICATION SCALE
• FREQ.+:
FREQUENCY POSITIVE FLOWRATE
• FREQ.-:
FREQUENCY NEGATIVE FLOWRATE
• FREQ.+/-:
FREQUENCY POSITIVE/NEGATIVE FLOWRATE
• :
PULSE POSITIVE FLOW RATE
• PULSES.-:
PULSE NEGATIVE FLOW RATE
• /-:
PULSE NEGATIVE/POSITIVE FLOW RATE
• BATCHING:
IT’S POSSIBLE TO SET A QUANTITY OF VOLUME THAT HAVE TO BE DELIVERED DURING
AN ACTUATOR (VALVE) OPENING-CLOSING CYCLE
Содержание B0A1C2B1A4A0
Страница 1: ...Type SE58 L Transmitter Operating Instructions...
Страница 8: ...7 English SE58 L Dimensions 200 114 164 167 114 180 290 195...
Страница 9: ...8 English SE58 L Remote version 142 28 295 120 7 30...
Страница 11: ...10 English SE58 L DIMENSIONS STAINLESS STEEL VERSION Compact Version 171 156 186 146...
Страница 12: ...11 English SE58 L Separate Version 236 40 7 90 241 55...