Technical Data
6.9
Resetting the device (Device Reset)
A restricted reset of the device to factory settings (Device Reset) can be performed using the:
•
PC Service Program
(see: „Software manual Type 8681 | PC service program“) for “classic” designs or
•
Bürkert Communicator
(for IO-Link and büS/CANopen design only) or
•
directly on the control head.
Procedure (directly at the control head):
→
Simultaneously actuate T1 + T2 + T3 (approx. 2.5 s long) to access the "Device Reset" mode – the cor
-
responding flashing pattern
depends on the design of the control head.
If the device is not reset 10 s after switching to the „Device Reset“ mode, this mode is automatically left.
→
Simultaneously actuate T1 + T2 + T3 again (approx. 2.5 s long) – this will reset the device for real. The
flashing pattern which
depends on the design of the control head, indicates that the device was reset –
see also chapter
“21.2 Flashing pattern & fault signalling” on page
Device Reset resets the following values to the factory settings:
•
Teach positions S1...S3
all positions
"not taught"
• Feedback fields from S1...S3
(see chapter “6.8.1” on page
• Resettable switching cycle counters V1...V3 (see chapter “6.8.2” on page
• Resettable operating duration
(see chapter “6.8.2” on page
• Service intervals switching cycles V1...V3
(see chapter “6.8.2” on page
• Service interval operating duration
(see chapter “6.8.2” on page
• Service/maintenance notification
(signaling of elapsed maintenance intervals)
inactive
(see chapter “6.8.2” on page
•
Magnetic manual override function
active
(see chapter “6.8.3” on page
)
• External initiator S4 in = NO
(see chapter “21.1.1” on page
)
•
Feedback external initiator S4 as S1
not active
(see "PC service program" software manual)
• Configurations client (only büS/CANopen)
automatic switching on
or
active
(see „15.14.4“)
• Service display option (only IO-Link, büS/C.)
service indication display option:
on
(see software
description)
Device Reset does not reset the following values (amongst others):
• all hardware configured values (i.e. set via DIP switches)
•
Switching cycle counter Total V1...V3
•
Operating duration Total
• AS-i address
(see chapter “12.9” on page
• AS-i profile
• DeviceNet Input Assembly
(see chapter “13.11.1” on page
)