98
büS/CAN open-Design
NOTE 1: How to restart the device
If the settings are changed by actuating the DIP switches, these changes will not take effect
until the device is restarted! For a restart:
• trigger a restart command via Bürkert Communicator or
• briefly disconnect the control head from the power supply and reconnect or
• switch the power supply off/on or
•
transmit an appropriate reset message.
NOTE 2: Special characteristics for the DIP switch setting DIP1 to DIP6 “000000”
•
This setting is the
factory setting,
i.e.
software configurable address/Node ID.
The further behaviour in the network depends on the “Static Node-ID”, see for this the following
explana tions.
•
Bus mode büS (bueS) or CANopen:
The behaviour with this DIP switch setting depends on the bus mode (büS (bueS) or CANopen).
The
factory setting is büS
(bueS). The bus mode can be changed by software only - see chapter
“15.20.4 Access to further parameters (cyclic and acyclic)” on page
•
Device addressing using software in the:
büS/bueS mode:
For the DIP switch position (DIP1 to DIP6 = 000000) the parameter
“Fixed CANopen address” (“Static Node ID”)
has a
factory setting of
“0” = “Auto addressing”
of the device address (CANopen address, Node
ID). On this occasion, the Node ID will be automatically configured (device
addresses from 1 to 127 are possible).
If the device is to receive a fixed device address, the
“Fixed CANopen
address” (“Static Node ID”)
must be set to the appropriate value using the
Bürkert Communicator. To accept this value, the device must be restarted.
If the device does not receive the “target” device address set as parameter
”Fixed CANopen address” , the solenoid valves remain in the configured
safety position and an error status is displayed.
If the “Fixed CANopen address” (“Static Node ID”) is reset to “0” (= “Auto
addressing”), the auto addressing starts after a restart with the last used
device address (Node ID).
When changing the configuration of the device address from “via DIP
switch” to “software configured”, the “Fixed CANopen address” (“Static
Node-ID”) is reset once to “0” (= “Auto addressing”) at the required restart.
Auto addressing starts a usual after a restart with the last used device
address (Node ID) .
In the
case of auto addressing,
the
interfaces
of the individual devices
have to be checked and possibly reassigned, e.g. via Bürkert Communi
-
cator – see software manual for Type 8920 (search therein for “büS network
configuration”/”büS map”), see chapter “4.3”
CANopen mode:
Software configurable device address / Node ID (from 1 to 127 is possible):
Consider for CANopen bus mode that a software configured Node ID of “0”
results in a device Node ID of “1”! But if two devices had the same address,
bus problems would result!
Please note:
Hardware-configured values (that means: set via DIP switches) overwrite software-
configured values!