65
DeviceNet - Design
13.6
Design aid
Power consumption of the electronics:
P
El
= 1.44 W
or
I
El
= 60 mA
at 24 V
Power consumption of a valve during activation (200 ms):
P
Valve-ON
= 0.9 W
or
I
Valve-ON
= 38 mA
at 24 V
Power consumption of a valve after reduction:
P
Valve
= 0.6 W
or
I
Valve
= 25 mA
at 24 V
Power consumption of an optical position report:
P
LED
= 1.0 W
or
I
LED
= 42 mA
at 24 V
Calculation examples:
Example 1:
3 valves are activated simultaneously, one position is reported (status for 200 ms):
P
Total
=
P
El
+ 3 x P
Valve-ON
+ 1 x P
LED
5.14 W =
1.44 W
+ 3 x 0.9 W
+ 1 x 1.0 W
or
I
Total
=
I
El
+ 3 x I
Valve-ON
+ 1 x I
LED
216 mA =
60 mA
+ 3 x 38 mA
+ 1 x 42 mA
Example 2:
3 valves have been activated simultaneously, one position is reported (persistent state):
P
Total
=
P
El
+ 3 x P
Valve
+ 1 x P
LED
4.24 W =
1.44 W
+ 3 x 0.6 W
+ 1 x 1.0 W
or
I
Total
=
I
El
+ 3 x I
Valve
+ 1 x I
LED
177 mA =
60 mA
+ 3 x 25 mA
+ 1 x 42 mA
When using an external initiator, its power requirement should be added.