145
LED Colour Assignments
Display of device status / errors / warnings
No.
Flashing pattern / colour
(for reasons of space the
“colour of the valve posi-
tion” is designated as
position colour
)
ON
OFF Note
Classic *)
NAMUR *)
VM *)
VM+E *)
VM+E+W *)
1
in position colour
100
ms
100
ms
3 x flashing:
Teach confirmation
x
x
x
x
x
(
after
successful teaching: colour for
position S1 and S2 continuously ON)
x
x
x
2
in error colour
100
ms
100
ms
3 x flashing:
- if target could not be located in the
measuring area during teaching or
- if teach position is too close
(±0.5 mm) to a previously defined
teach position or
- if magnetic manual override is
used, even though manual override
function was disabled by software
x
x
x
x
x
3
in position colour
125
ms
125
ms
Continuous flashing:
Signal from the external initiator S4
(factory settings – comp.
x
x
x
x
4
in position colour
250
ms
250
ms
Continuous flashing:
Signal from position S3 (factory set
-
x
x
x
x
5
in error colour
250
ms
250
ms
Continuous flashing:
- Teaching does not occur or
- Automatic Teach function
(Autotune) error or
- Teach Reset implemented or
- Bus error or
- Position measuring system signal
error (from firmware
B.02.00.00) or
- Device Reset implemented
x
6
in error colour
50
ms
450
ms
Continuous flashing:
Device in service mode /
manual override active
x
7
in error colour
450
ms
50
ms
Continuous flashing:
Internal error
x
english
Control Head Type 8681
Содержание 8681
Страница 115: ...115 büS CAN open Design T h i s parameter is displayed for all devices english Control Head Type 8681 ...
Страница 165: ...165 english Control Head Type 8681 ...