119
büS/CAN open-Design
LED
Device status
possible errors
Remedy
Red
Error
- it is critical if
the LED
is still lit 2
minutes after
the last device
restart
•
Another device with the same
Node ID is in the same network
• No bus connection (Gateway /
PLC) due to communication
problems or gateway restart
•
Check baud rate
• Check the Node ID address (if
required, correct it so that each
address is only available once)
•
Check the status of the gateway
connected to the system
• If required, replace the device
*)
Display/visualisation only from firmware version B.02
15.22
Firmware updates
Firmware updates of the control heads, gateways (and possibly other devices) can only be carried out using
the Bürkert Communicator with the aid of a büS stick. This requires the “installer level”.
The integration of the Bürkert Communicator into the network can be seen, for example, in
The firmware is stored in the Bürkert Communicator and is kept up to date via updates.