76
IO-Link - Design
14.2
Quickstart for Type 8681 IO-Link
Network layout:
IO-Link devices are connected with standard commercial IO-Link masters and can easily be integrated into
all commonly used fieldbus and automation systems.
The network is structured similarly to the diagram in
3-pin or 5-pin unshielded standard cables 20 m in length between the IO-Link device and IO-Link master
are sufficient for connecting IO-Link devices with IO-Link masters.
The IO-Link control heads are either equipped with M12 connectors (variant with multi-pole plug) or can be
wired themselves (variant with cable gland). For details see “14.5”
.
Configuration:
The network is configured by the higher-level controller.
To ensure clear communication, IO-Link devices should
not be parametrised simultaneously
by the higher-
level controller (PLC) via the IO-Link master
and
with the Bürkert Communicator (via the service interface).
See details in
Software download / firmware updates:
Download the required software files / IODD and the object description from:
/ search term: 8681 / Downloads / Software / “Initiation Files EDS IODD” (zip file).
See details in chapter
14.3
Technical data / specification
IO-Link specification:
Version 1.1.2
Port class:
A:
shared power supply (Power 1) for supply of the system and
actuators (solenoid valves)
or
B:
Separate power supply for the system (Power 1) and for
the actuators/solenoid valves (Power 2)
Power supply:
Port class
A:
via IO-Link port (M12x1, 4-pole A-coded);
Port class
B:
via IO-Link port (M12x1, 5-pole, A-coded),
for details see chapter
)
Operation mode:
IO-Link operation mode (SIO operation mode is not supported)
IODD file:
Download from: www.burkert.com / Type 8681 / Downloads /
Software (“Initiation Files” - zip file)
VendorID:
0x78,
120
DeviceID:
See relevant IODD file (port class A or B)
Transmission speed
COM3 (230.4 kbit/s)
M sequence type in Operate Mode:
TYPE_2_V
Min. cycle time:
2
ms
Data storage:
yes
Max. line length:
20 m between IO-Link master and IO-Link device
english
Control Head Type 8681