IO-Link - Design
14.4
IO-Link master / communication / configuration
IO-Link master
IO-Link masters are used as the interface between the control heads Type 8681 (IO-Link) and the higher-
level controller. All commonly used IO-Link masters in accordance with the specification (see chapter
“14.3”) can be used.
The “addressing” of the IO-Link devices is defined by the connection or port on the IO-Link master – This must
be noted when replacing the devices or master.
Communication / configuration / parametrisation
After the network has been set up (see for example “14.1 Network principle / interfaces”) and the correct
software has been installed in the IO-Link devices (IODD taking into consideration the port class) the network
is configured using the higher-level controller.
As described in chapter
, an IO-Link control head can also be connected in parallel to the IO-Link port
with the Bürkert Communicator (Type 8920) via the service interface (Micro-USB) on the electronic module
(see “Fig. 36” on page
To ensure clear communication, IO-Link devices should
not be parametrised simultaneously
by the higher-
level controller (PLC) via the IO-Link master
and
with the Bürkert Communicator (via the service interface).
14.5
Electrical data form the control head (IO-Link)
14.5.1
Electrical connection options / interface
or
with cable glands
or
with cable glands and multi-pole connection
(M12 connection in accordance with IEC 61076-2-101,
4-pole (port class A) or 5-pole (port class B),
cable length approx. 15 cm
Connection left: voltage, signals (IO-Link port)
Connection right: external initiator
Fig. 35: Connection options
Connections:
Cable gland variant:
1 x M16 x 1.5 cable gland / size22 – for power supply and signals (IO-Link);
only for transportation safety device sealed with dummy plugs, remove these
before use) for cable diameter 5 ... 10 mm, for wire cross-sections 0.14 ...
1.5 mm
2
1 x M16 x 1.5 cable gland/size19 – connection option for external proximity
switch (sealed with dummy plug, remove this before use)
Variant multi-pole connection: 1 x M16 x 1.5 cable gland/size22 with M12 connector in accordance with IEC
61076-2-101, 4-pole (port class A) or 5-pole (port class B) for power supply
and signals (IO-Link), cable length approx. 15 cm
1 x M16 x 1.5 cable gland/size19 – connection option for external proximity
switch (sealed with dummy plug, remove this before use)
english
Control Head Type 8681