Service Mode / Manual override
22
SERVICE MODE / MANUAL OVERRIDE
By default, the control head provides the following (e.g. for service purposes):
•
a
magnetic manual override
which is easily accessible from the outside for solenoid valve 1 (2/A1)
*)
as
well as
•
a
mechanical manual override
accessible when the hood is open on each equipped solenoid valve –
see chapter
“22.2 Mechanical manual override”
.
22.1
Magnetic manual override
Magnetic manual
override tool
Markings for
magnetic
manual override
Fig. 49:
Magnetic manual override / magnetic manual override tool on the basis of encoded magnetic fields
Irrespective of the signal of the higher-level control, the magnetic manual override sets in the
Automatic mode
the output of the solenoid valve V1
*)
electrically to an ON signal and, if control pressure is present, switches
the 2/A1 output
*)
,
in manual operating status,
the manual override
cannot
be used.
However, if the output of solenoid valve 1
*)
is activated by the control (ON signal from the higher-level
control), this switching status cannot be set to an OFF signal with the manual override!
Activation/deactivation of this function is possible using the PC service program.
The factory setting
is
“magnetic manual override function active”, i.e. the function can be used, it is not disabled.
The connection to the PC is made via the service interface. Details are described in the “PC Service
Program Type 8681” software manual under the “SYSTEM/Start-up” menu option (for the IO-Link and büS/
CANopen design, the changeover can be carried out via the Bürkert Communicator).
Caution!
When the magnetic manual override (solenoid valve 1
*)
) will be actuated:
•
the peripheral fault bit is set on the AS interface design.
•
the mode is switched to "Manual override active" for the DeviceNet design and can be read out.
• the feedback signals (valve positions S1-3, external initiator) function as per normal operation.
Always observe the safety guidelines and the system statuses!
________________________
*)
both solenoid valves are actuated simultaneously for the design for double-acting actuators (see chapter
english
Control Head Type 8681