28
Technical Data
6.8
Factory settings in the firmware
The control head is supplied with the firmware factory settings as listed below.
Changes to the factory settings
for the
classic variants
of Type 8681
(24 V DC, 120 V AC, AS-i, DeviceNet)
are possible via the PC service program (see software manual: “Software manual Type 8681 | PC service
program”).
To do so, the control head is connected to the PC via the service interface on the electronic module – see
„Fig. 9“. This involves removing the plastic cover (see chapter „8“).
The service interface may only be used in non-explosive atmosphere, because the plastic hood
should be removed (see chapter “8 Opening and Closing the Housing”).
Changes to the factory settings
for the
variants DeviceNet, büS/CANopen and IO-Link
are usually pos-
sible via the bus-specific communication interface. With büS/CANopen and IO-Link, changes can also be
carried out via the Bürkert Communicator (Type 8920).
6.8.1
Feedback fields (position measuring system)
A feedback field is the area within which a valve position (e.g. S1) is reported back.
Signal of
the valve
position
Feedback field at top / positive
Feedback field at bottom / negative
Factory setting
[mm]
Adjustment range
[mm]
Factory setting
[mm]
Adjustment range
[mm]
S1
+ 3.00
+ 10.00 ... + 0.50
- 3.00
- 0.50 ... - 10.00
S2
+ 3.00
+ 10.00 ... + 0.50
- 3.00
- 0.50 ... - 10.00
S3
+ 1.00
+ 10.00 ... + 0.50
- 1.00
- 0.50 ... - 10.00
Stroke
[mm]
Feedback
field S1
[mm]
Target
(Reference:
upper edge
of the target)
Ensure that the teach points
including their feedback fields are
within the measuring range.
Fig. 8:
Schematic diagram (not to scale) of the feedback fields, using the example of valve position S1
Overlaps of S1/S2/S3 are possible (see chapter “21.3 Signal priorities”).
english
Control Head Type 8681