100
büS/CAN open-Design
15.14.4
Central configuration management (Configuration client)
As of firmware B.01.00.00 the central configuration management (e.g. with gateway ME43, as of firmware
A.03.02) is supported. This means that defective Bürkert devices can be exchanged easily, almost without
configuration effort. To do this, the configuration management for the configuration provider (gateway)
in the
Bürkert Communicator must be set to “Active”
and
the
“Configuration client”
parameter for the configuration
device (control head) must be set to mode “Automatically switch on” (= factory setting) or “Active” (Bürkert
Communicator:
Control Head / General settings / Parameters / Configuration client / Mode).
Via a memory card in the ME43 gateway, the last stored device parameters and configurations are retained
and can be transferred to the new Bürkert device.
When replacing a defective control head, however, the
hardware settings (all DIP switches)
must be set on
the new device
before
connecting to the network, as they have been set on the device which is to be replaced.
In this way, all relevant software parameters (during the communication process lasting several minutes to
integrate the new control head into the network) can be transferred automatically. The new device must then
be “taught”.
Details and operating conditions are described in the software manual “Central configuration management
of Bürkert devices” (see chapter “4.3” on page
For this configuration the Bürkert Communicator version 4.x or higher is required.
(During a device reset / factory reset of the configuration device (control head, as of firmware B.01.00.00), the
“configuration client”
parameter mode is reset to the factory setting “Automatically switch on”.)
15.15
Changing the gateway IP address
Each gateway requires a unique IP address to distinguish several gateways from each other.
If required, the gateway IP address can be changed directly at the gateway itself using its menu and arrow
keys or in four other ways:
using
web server
(“15.15.1”) or
Bürkert Communicator
or
Logix Designer
(“15.15.3”), please
use the LogixDesigner manual for this) or
RS Linx
After changing the gateway IP address, register (“15.16”) and install the gateway using Logix Designer (see
“15.17”).
The gateway must always be connected to the same network as the PC!
15.15.1
Changing the gateway IP address using web server
→
Call the gateway’s web server with
a browser (enter only the current IP
address number:
“http://192.168.1.100”)
(the window which opens for this IP
address shows the default
“Static IP address” of all gateways ME43
(factory setting):
192.168.1.100)
→
Then click “Login”
english
Control Head Type 8681