MAKSİCONDENSE 48-65
Notes
01/2018
90
Training 0020260859_00
3.3.6.6 Dry fire test by NTC
1. Test for temperature change without burner operation
The dry fire test can already be successful during unit start-up without burner operation.
Testing process:
If the burner is not in operation and the measured temperature value at T flow is > 110
°C or at T
return is > 110
°C, the burner is blocked and only the pump is started until the current measured
temperature has fallen to < 80
°C. The burner is then released again.
2. Test for temperature change with burner operation
Testing process
If the burner is in operation (flame recognised) and the measured temperature value at T flow is >
97
°C or at T return is > 97 °C, the burner is stopped and blocked, the unit pump continues running
until the current measured temperature has fallen to < 80
°C. The burner is then released again.
3.3.6.7 Low-water pressure protection
Temperature rise too rapid
If the flow temperature or return temperature rises quicker than 10 K/s, the unit cuts out for 10
minutes and then attempts to restart. During the block, the status message
"S.54"
appears in the
display. After the fourth failed attempt in a row, the unit is shut down and locked. The fault message
"F.24"
is displayed.
Temperature difference too great
If the temperature difference between the flow and return NTC is greater than 30 K > 3 sec, the unit
operates with a minimum load for 10 minutes (status message
"S.53"
in the display). If the difference
of 35 K is measured, a block is imposed for 10 minutes (status message
"S.53"
in the display) and,
after five subsequent attempts (to increase operating safety), a locking switch-off sequence is trig-
gered with
"F.23"
.
3.3.6.8 Determining the volume flow
See section 3.3.5.1 and following sections.
3.3.6.9 Test during operation
1. Monitoring the flame signal. Up to five ignition attempts possible.
2. Monitoring the 230
± 5 V electric power supply
Содержание Thema Condens AS 48-A
Страница 1: ...DEM RD K M MAKS CONDENSE 48 65...
Страница 2: ......
Страница 5: ...8 4 2 Gas consumption relating to nominal load 191 8 5 System checklist 192...
Страница 6: ......
Страница 12: ...MAKS CONDENSE 48 65 Notes 01 2018 6 Training 0020260859_00...
Страница 28: ...MAKS CONDENSE 48 65 Notes 01 2018 22 Training 0020260859_00...
Страница 44: ...MAKS CONDENSE 48 65 Notes 01 2018 38 Training 0020260859_00...
Страница 110: ...MAKS CONDENSE 48 65 Notes 01 2018 104 Training 0020260859_00...
Страница 122: ...MAKS CONDENSE 48 65 Notes 01 2018 116 Training 0020260859_00...
Страница 124: ...MAKS CONDENSE 48 65 Notes 01 2018 118 Training 0020260859_00 C43P C53 C83 C83P C93 C63...
Страница 146: ...MAKS CONDENSE 48 65 Notes 01 2018 140 Training 0020260859_00...
Страница 156: ...MAKS CONDENSE 48 65 Notes 01 2018 150 Training 0020260859_00 6 4 Regional legislation...
Страница 182: ...MAKS CONDENSE 48 65 Notes 01 2018 176 Training 0020260859_00...
Страница 192: ...MAKS CONDENSE 48 65 Notes 01 2018 186 Training 0020260859_00 8 3 ErP data Data sheet that is enclosed with the product...
Страница 193: ...MAKS CONDENSE 48 65 Notes 03 2020 187 TEKN K E T M VE DESTEK...
Страница 196: ...MAKS CONDENSE 48 65 Notes 01 2018 190 Training 0020260859_00...