MAKSİCONDENSE 48-65
Notes
01/2018
76
Training 0020260859_00
3.3.5.2 New! Control function of the remaining pump head, temperature target value limita-
tion
Modulation limitation max.
°C
1. Zone:
No circulation water volume (OFR). Max. Temperature target value not enabled as the
minimum volume flow of
125 l/hr
per heat exchanger coil is not fulfilled. The burner therefore
remains locked and the unit start is blocked.
2. Zone:
Low circulation water volume (LFR). The max. Temperature target value is enabled for a
flow temperature of
max. 65
°C
. This corresponds to a volume flow of
125 l/hr
to
350 l/hr
per
heat exchanger coil. The burner is therefore enabled and the boiler starts and modulates within
the temperature limitation of
65
°C
.
3. Zone:
High circulation water volume (HFR). The temperature target value is enabled for a max.
Temperature of
max.
85
°C
. That corresponds to a volume flow
> 350 l/hr
per heat exchanger
coil. The burner now operates without a special temperature limitation.
With the control functions, SDBG can ensure a continuous operation of the unit
without operating blocks while supplying heat.
Furthermore, the number of switching cycles during operation is minimised (preven-
tive maintenance).
No flow rate/no igni-
tion
35
–65 kW
Low flow rate 35
–65 kW
(LFR)
High flow rate 35
–65 kW
(HFR)
Volume flow per heat exchanger coil and temperature difference limitation
Te
mpe
ra
tu
re
[
°C
]
Volume flow per coil [l/hr]
Temperature difference 35–65 kW
Boiling range
Содержание Thema Condens AS 48-A
Страница 1: ...DEM RD K M MAKS CONDENSE 48 65...
Страница 2: ......
Страница 5: ...8 4 2 Gas consumption relating to nominal load 191 8 5 System checklist 192...
Страница 6: ......
Страница 12: ...MAKS CONDENSE 48 65 Notes 01 2018 6 Training 0020260859_00...
Страница 28: ...MAKS CONDENSE 48 65 Notes 01 2018 22 Training 0020260859_00...
Страница 44: ...MAKS CONDENSE 48 65 Notes 01 2018 38 Training 0020260859_00...
Страница 110: ...MAKS CONDENSE 48 65 Notes 01 2018 104 Training 0020260859_00...
Страница 122: ...MAKS CONDENSE 48 65 Notes 01 2018 116 Training 0020260859_00...
Страница 124: ...MAKS CONDENSE 48 65 Notes 01 2018 118 Training 0020260859_00 C43P C53 C83 C83P C93 C63...
Страница 146: ...MAKS CONDENSE 48 65 Notes 01 2018 140 Training 0020260859_00...
Страница 156: ...MAKS CONDENSE 48 65 Notes 01 2018 150 Training 0020260859_00 6 4 Regional legislation...
Страница 182: ...MAKS CONDENSE 48 65 Notes 01 2018 176 Training 0020260859_00...
Страница 192: ...MAKS CONDENSE 48 65 Notes 01 2018 186 Training 0020260859_00 8 3 ErP data Data sheet that is enclosed with the product...
Страница 193: ...MAKS CONDENSE 48 65 Notes 03 2020 187 TEKN K E T M VE DESTEK...
Страница 196: ...MAKS CONDENSE 48 65 Notes 01 2018 190 Training 0020260859_00...