MAKSİCONDENSE 48-65
Notes
03/2020
111
T
EKNİK EĞİTİM VE DESTEK
5.2 Product requirements
5.2.1 Minimum clearances
Minimum clearances
Min. clearances
A
275 mm
: 80/125 mm
diameter
LAF
LAF = air/flue pipe
B
180 mm
; optimal approx. 250 mm
C
5 mm
; optimal approx. 50 mm
D
500 mm
; clearance for unit maintenance that is required to open the front of the unit.
No clearance is required between the unit and components made of combustible parts because the
temperature at the unit's nominal heat output never exceeds the maximum permissible temperature
of
85 °C
.
Lateral clearance is not required, but the side sections can also be removed if there is adequate side
clearance (at least approx. 50 mm) to facilitate maintenance or repair work.
Содержание Thema Condens AS 48-A
Страница 1: ...DEM RD K M MAKS CONDENSE 48 65...
Страница 2: ......
Страница 5: ...8 4 2 Gas consumption relating to nominal load 191 8 5 System checklist 192...
Страница 6: ......
Страница 12: ...MAKS CONDENSE 48 65 Notes 01 2018 6 Training 0020260859_00...
Страница 28: ...MAKS CONDENSE 48 65 Notes 01 2018 22 Training 0020260859_00...
Страница 44: ...MAKS CONDENSE 48 65 Notes 01 2018 38 Training 0020260859_00...
Страница 110: ...MAKS CONDENSE 48 65 Notes 01 2018 104 Training 0020260859_00...
Страница 122: ...MAKS CONDENSE 48 65 Notes 01 2018 116 Training 0020260859_00...
Страница 124: ...MAKS CONDENSE 48 65 Notes 01 2018 118 Training 0020260859_00 C43P C53 C83 C83P C93 C63...
Страница 146: ...MAKS CONDENSE 48 65 Notes 01 2018 140 Training 0020260859_00...
Страница 156: ...MAKS CONDENSE 48 65 Notes 01 2018 150 Training 0020260859_00 6 4 Regional legislation...
Страница 182: ...MAKS CONDENSE 48 65 Notes 01 2018 176 Training 0020260859_00...
Страница 192: ...MAKS CONDENSE 48 65 Notes 01 2018 186 Training 0020260859_00 8 3 ErP data Data sheet that is enclosed with the product...
Страница 193: ...MAKS CONDENSE 48 65 Notes 03 2020 187 TEKN K E T M VE DESTEK...
Страница 196: ...MAKS CONDENSE 48 65 Notes 01 2018 190 Training 0020260859_00...