MAKSİCONDENSE 48-65
Notes
03/2020
169
T
EKNİK EĞİTİM VE DESTEK
Display
Text display (description)
Possible cause
F.71
Fault: Flow sensor
(flow sensor reports a constant value)
Flow sensor not correctly positioned on the
flow pipe.
Flow sensor defective.
F.72
Fault: Flow/return sensor
Flow and/or return sensor defective (toler-
ances too great)
F.73
Fault: Water press. sensor
(water pressure sensor signal in the
wrong range (too low))
Line break in water pressure sensor line or
Short circuit to 0 V or
Water pressure sensor defective
F.74
Fault: Water press. sensor
(water pressure sensor signal outside
correct range (too high))
Line to water pressure sensor has short circuit
to 5 V/24 V or
Internal fault in water pressure sensor
F.75
Fault: Pump/water deficiency
(no pressure change detection when
starting pump)
Water pressure sensor and/or pump defective
Air in the heating system
Insufficient water in unit;
check external bypass;
External expansion vessel connected on flow
line
D.149 = 1 Pump blocked alarm
Clean the pump; replace the pump
D.149 = 2 Electrical pump fault
Check supply voltage; replace the pump
D.149 = 3 Pump dry fire
Check system pressure; make sure there is no
remaining air in the system.
Replace the pump
D.149 = 5 No pump jump detected
Check pressure sensor; replace pressure sen-
sor
D.149 = 6 No PWM response from
pump
Check the pump cable harness; check the
PCB; check the plug connections;
check the supply voltage; replace the pump;
replace the PCB
D.149 = 7 Incorrect pump detected
The detected pump does not match the unit
–
pump does not have a reliable identification
code; use the pump from the matching spare
parts programme
D.149 = 8 Volume flow test after
purging programme
not successful
Check that all locks are open or open thermo-
static valves; check system pressure (
≥ 1.5
bar)
F.77
Fault: Flue non-return flap/conden-
sate pump (water level in condensate
pump/no return signal (bridge) from
"2 in 7" accessory module)
Condensate pump defective
Cable connection defective
Содержание Thema Condens AS 48-A
Страница 1: ...DEM RD K M MAKS CONDENSE 48 65...
Страница 2: ......
Страница 5: ...8 4 2 Gas consumption relating to nominal load 191 8 5 System checklist 192...
Страница 6: ......
Страница 12: ...MAKS CONDENSE 48 65 Notes 01 2018 6 Training 0020260859_00...
Страница 28: ...MAKS CONDENSE 48 65 Notes 01 2018 22 Training 0020260859_00...
Страница 44: ...MAKS CONDENSE 48 65 Notes 01 2018 38 Training 0020260859_00...
Страница 110: ...MAKS CONDENSE 48 65 Notes 01 2018 104 Training 0020260859_00...
Страница 122: ...MAKS CONDENSE 48 65 Notes 01 2018 116 Training 0020260859_00...
Страница 124: ...MAKS CONDENSE 48 65 Notes 01 2018 118 Training 0020260859_00 C43P C53 C83 C83P C93 C63...
Страница 146: ...MAKS CONDENSE 48 65 Notes 01 2018 140 Training 0020260859_00...
Страница 156: ...MAKS CONDENSE 48 65 Notes 01 2018 150 Training 0020260859_00 6 4 Regional legislation...
Страница 182: ...MAKS CONDENSE 48 65 Notes 01 2018 176 Training 0020260859_00...
Страница 192: ...MAKS CONDENSE 48 65 Notes 01 2018 186 Training 0020260859_00 8 3 ErP data Data sheet that is enclosed with the product...
Страница 193: ...MAKS CONDENSE 48 65 Notes 03 2020 187 TEKN K E T M VE DESTEK...
Страница 196: ...MAKS CONDENSE 48 65 Notes 01 2018 190 Training 0020260859_00...