Notes
01/2018
70
Training 0020260859_00
3.3.4.9 Burner anti-cycling time for heating mode
The burner anti-cycling time limits the number of switching cycles in Heating mode. It is started when
the heat demand signal (terminals 3
–4 VR 36, eBUS or internal regular shutdown) no longer exists.
Effective burner anti-cycling time:
Calculated
Flow temperature
Set maximum burner anti-cycling time
1
5
10
15
20
25
30
35
40
48
50
55
60
20
2.0 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 48.0 50.0 55.0 60.0
25
2.0 4.5 9.2
14.0 18.5 23.0 27.5 32.0 36.5 41.0 48.0 50.0 54.5
30
2.0 4.0 8.5
12.5 16.5 20.5 25.0 29.0 33.0 37.0 41.0 48.0 49.5
35
2.0 4.0 7.5
11.0 15.0 18.5 22.0 25.5 29.5 33.0 36.5 40.5 44.0
40
2.0 3.5 6.5
10.0 13.0 16.5 19.5 22.5 26.0 29.0 32.0 35.5 38.5
48
2.0 3.0 6.0
8.5
11.5 14.0 17.0 19.5 22.5 25.0 27.5 30.5 33.0
50
2.0 3.0 5.0
7.5
9.5
12.0 14.0 16.5 18.5 21.0 23.5 25.5 28.0
55
2.0 2.5 4.5
6.0
8.0
10.0 11.5 13.5 15.0 17.0 19.0 50.5 55.5
60
2.0 2.0 3.5
5.0
6.0
7.5
9.0
10.5 11.5 13.0 14.5 15.5 17.0
65
2.0 1.5 2.5
3.5
4.5
5.5
6.5
7.0
8.0
9.0
10.0 11.0 11.5
70
2.0 1.5 2.0
2.5
2.5
3.0
3.5
4.0
4.5
5.0
5.5
6.0
6.5
75
2.0 1.0 1
1
1
1
1
1
1
1
1
1
1
─
The anti-cycling time is calculated from the target flow temperature and the maximum burner
anti-cycling time that is set.
─
Domestic hot water mode being on during the burner anti-cycling time does not influence the
timing element.
─
The timing element can be reset using the menu item
"Reset anti-cycl. time"
in the user
menu or by pressing the mains switch.
─
The maximum burner anti-cycling time can be adjusted under diagnostics code
"D.002"
between two and 60 minutes (factory setting 20 mins).
─
The remaining burner anti-cycling time after a regular shutdown in heating mode can be
called up under the menu item
"Reset anti-cycl. time"
in the user menu.
3.3.4.10 Frost protection mode
If the flow
temperature (measured on the flow temperature NTX) falls below a value of 8 °C, for 30
minutes:
─
The prioritising diverter valve is moved to a mid-position between heating mode and domestic
hot water mode
─
The heating pump is switched on.
This sends current temperature values to the flow temperature NTC from the heating installation and
the heating water is mixed. If the flow temperature exceeds 10 °C, the pump is switched off again
before the end of the 30 minutes. At the end of the 30 minutes or if the flow temperature falls below
5 °C, the burner is operated with the partial heat load set. Heating mode is switched off if the flow
temperature exceeds 35 °C.
Frost protection mode ends irrespective of the aforementioned measures, if:
1. Domestic hot water mode or
2. Heating mode is requested.
Содержание Thema Condens AS 48-A
Страница 1: ...DEM RD K M MAKS CONDENSE 48 65...
Страница 2: ......
Страница 5: ...8 4 2 Gas consumption relating to nominal load 191 8 5 System checklist 192...
Страница 6: ......
Страница 12: ...MAKS CONDENSE 48 65 Notes 01 2018 6 Training 0020260859_00...
Страница 28: ...MAKS CONDENSE 48 65 Notes 01 2018 22 Training 0020260859_00...
Страница 44: ...MAKS CONDENSE 48 65 Notes 01 2018 38 Training 0020260859_00...
Страница 110: ...MAKS CONDENSE 48 65 Notes 01 2018 104 Training 0020260859_00...
Страница 122: ...MAKS CONDENSE 48 65 Notes 01 2018 116 Training 0020260859_00...
Страница 124: ...MAKS CONDENSE 48 65 Notes 01 2018 118 Training 0020260859_00 C43P C53 C83 C83P C93 C63...
Страница 146: ...MAKS CONDENSE 48 65 Notes 01 2018 140 Training 0020260859_00...
Страница 156: ...MAKS CONDENSE 48 65 Notes 01 2018 150 Training 0020260859_00 6 4 Regional legislation...
Страница 182: ...MAKS CONDENSE 48 65 Notes 01 2018 176 Training 0020260859_00...
Страница 192: ...MAKS CONDENSE 48 65 Notes 01 2018 186 Training 0020260859_00 8 3 ErP data Data sheet that is enclosed with the product...
Страница 193: ...MAKS CONDENSE 48 65 Notes 03 2020 187 TEKN K E T M VE DESTEK...
Страница 196: ...MAKS CONDENSE 48 65 Notes 01 2018 190 Training 0020260859_00...