4
Tank Assembly
Logalux PL750/2 S - Changes may be made following technical improvements!
13
4.1.5
Installation of tank kit components
V
Attach a note to discharge piping saying: “Do not close
off discharge. Water can discharge from piping during
operation".
V
Size discharge piping to conform with relief valve dis-
charge dimension (Tab. 3).
V
Periodically verify proper relief valve operation.
Fig. 11 Tank kit connections on solar combi-tank
1
Cap for DHW recirc connection
2
T piece with P & T valve
Danger:
Personal and system damage due
to incorrectly installed relief valve discharge
line!
V
Pipe relief valve discharge piping full port
to nearest floor drain. (Maximum length:
6 ft and maximum 2 ea. 90° elbows).
Minimum pipe size
Water volume
Max. coil input
l
gal
kW
BTU
¾ NPT
200 – 400
53 – 103
58
198,000
Tab. 3
Sizing of the P & T valve discharge line